Page 487 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 487

6

                                                                                                                    485



                    System bus   1: RD+/TD+
                  Input              Output  2: RD--/TD--                       Block diagram of an input
                                 3: TD--/RD--
                   4        4
                  1  5  3  3  5  1  4: TD+/RD+                       Analog Input                       Supply
                   2        2    5: GND
                                 Housing: Shield                     X1 ... X4
                       M12 B coded
                                                                      M12                                M12
                                                                       1                                  1
                    Analog Inputs  1: 24 V U                           2                A/D       Logic
                      X1 ... X4  2: Input +  LS
                                                                       4
                  1  2     2  3            +     +
                   5        5
                  4  3     1  4  5: Shield  _    _
                                                                       3                                  3
                       M12 A coded                                        10 nF  270 pF        Ch    Er
                                 4: Input -                                                    1 ... 4  1 ... 4
                                 3: 0 V U                        Shield  5
                                     LS
                                 Housing: Shield
                      Supply     1: 24 V U                                                              Module
                   Input               Output  2: 24 V U LS                                              mount
                                 3: 0 V U  A
                   2        2        LS
                  3  1    1  3   4: 0 V U A
                   4        4
                       M12 A coded




           Technical Data                                       Technical Data
           Analog value creation:                               Isolation:                                          6
            Resolution              16 bits                       Channel – Channel       No
            Conversion method       SAR                           U LS , U A , system bus  500 V DC each
            Monotonicity without error code  yes                Configurable functions:
            Conversion time         1 ms                          Measuring range (per channel)  0-20 mA, 4-20 mA, ±20 mA, 0-10 V,
            Sampling delay          1 ms (module)                                         ±10 V, user-defined
                                    < 100 μs (channel/channel)    Limiting values (per channel)  Min./Max.
            Sampling repeat time    1ms                           Input filter (per channel)  50 Hz / 60 Hz / filter off
           Failures and errors:                                   Substitute value (per channel)  Value
            Voltage proof           up to 32 V (internal current limitation)  Online simulation (per channel)  Lock/unlock; simulation value: (according
            Max. measuring error at 25°C  ≤ ± 0.2 % of the measuring range                to measuring range)
            Temperature error       ≤ 100 ppm/K of measuring range  Online simulation (per channel/
            Maximum error over the full                           module)                 Diagnostics
            temperature range       ≤ ± 0.6 % of the measuring range  I/O diagnostics:
           System bus:                                            I/O diagnostics (per channel)  Overrange/measuring range underflow
            Connection type (3)     M12 connectors, B coded, 5 poles,                     and wire break at 4-20 mA
                                    shielded                                              Overcurrent
           Standards and approvals:                                                       Limit value violation (min/max)
            Conformity marking      1                             I/O diagnostics (per module)  Short circuit/overload (sensor supply)
            Korea Certification                                                           undervoltage (U LS  + U A )
            r UL 508                                            Process image:
                                                                  Process data width      8-byte data + status
                                                                LED indicators:
                                                                  SB: System bus status   LED (green/red/orange)
                                                                  F: Error status         LED (red)
                                                                  Ch1 ... Ch4: Input signal status  LED (yellow)
                                                                  Er1 ... Er4: Input signal error  LED (red)
                                                                  U LS  + U A : Supply status  LED (green)
                                                                  Indicators              Non-latching








                                                                General Specifications
                                                                Dimensions (mm) W x H x L  50 x 35.7 x 117
                                                                Weight                    262 g
   482   483   484   485   486   487   488   489   490   491   492