Page 483 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 483

6

                                                                                                                    481



                     System bus     1: RD+/TD+
                    Input               Output  2: RD--/TD--                  Block diagram of an input/output
                                    3: TD--/RD--
                                    4: TD+/RD+
                                    5: GND                           Digital Input/Output               Supply
                                    Housing: Shield                  X1 ... X8
                     M12 B coded
                                                                     M12                                 M12
                                                                                                          2
                                                                      3              Diagnostics sensor/actuator supply  4
                  Digital Inputs/Outputs   1: 24 V                    1
                      X1 ... X8   3: 0 V U A                                              Input 0 ... 7
                                                                                                      10 nF  10 nF
                                                                                                Logic
                                                                                          Output 0 ...7
                                                                      4
                     M12 A coded
                                  4: In-/Output
                                  2: n.c.
                                                                                           Input/Output  Error
                                                                                             0 ... 7  F
                                                                        10 nF  270 pF
                       Supply       1: 24 V U
                    Input               Output  2: 24 V U LS
                                    3: 0 V U  A
                                    4: 0 V U LS
                                        A
                                                                                                         Module
                                                                                                          mount
                     M12 A coded


           Technical Data                                       Technical Data
           Digital outputs:                                     Counters:                                           6
            No. of outputs          8                             No. of counters         2
            Connection type (2)     M12 connectors, A coded, 4 poles  Counter type        Event/gate time counter, pulse duration
            Wire connection         2- or 3-wire                  Counting/switching frequency  0 Hz ... 1 kHz
            Output voltage          ≤ U A                       System bus:
            Output current (per channel)  0.5 A (max. 0.6 A),     Connection type (3)     M12 connectors, B coded, 5 poles, shielded
                                    short-circuit/overload proof   Standards and approvals:
                                    (thermal disconnection)       Conformity marking      1
            Voltage drop against U A  at 500 mA  max. 0.2 V DC    Korea Certification
            Output current (module)  max. 4 A                     r UL 508
            Leakage current in OFF state  typ. 5 μA             Isolation:
            Output circuit          High-side switching           Channel – Channel       no
           Information on actuator selection:                     U LS , U A , system bus  500 V DC each
            Delay time hardware from "0" to "1"                 Configurable functions:
            (0 – 90%)               typ. 70 μs (resistive load)   Operating mode (per module)  DO-Module/DI-Module/DIO-Module/
            Delay time hardware from "1" to "0"                                           DIO + 1 counter/DIO + 2 counters
            (0 – 90%)               typ. 180 μs (resistive load)  Counter                 Count direction, start/limit value switching
            Rise time from "0" to "1"  typ. 40 μs (resistive load)                        output, gate time
            Fall time from "1" to "0"  typ. 40 μs (resistive load)  Input filter (per channel)  0.1/ 0.5/ 3 /15 /20 ms/ filter off
            Cable length, unshielded  ≤ 30 m                      Inversion (per channel)  On/off
            Reverse current (in case of recovery for              Substitute value strategy (per channel)  Switch substitute value/hold last value
            voltages > U A )        ≤ 0,5 A (error: 1 channel)    Substitute value (per channel)  0/1
            Type of load            Inductive, resistive loads and lamps  Manual mode (per channel)  On/off
            Switching frequency     Inductive load approx. 20 Hz   Manual mode value (per channel)  0/1
                                    Resistive load approx. 500 Hz   Online simulation (per channel)  Lock/unlock; simulation value: 0/1
                                    Lamp load approx. 500 Hz      Online simulation (per channel/module)  Diagnostics
            Parallel connection of 2 outputs  for power boost   I/O diagnostics:
                                    for redundant actuation of a load  I/O diagnostics (per channel)  Overtemperature
            Type of protective circuit  External protection (e.g., recovery diodes)  I/O diagnostics (per module)  Sensor/Actuator supply short-circuit/
            Output resistance       < 0.4 Ω                                               overload; Undervoltage (U LS  + U A )
           Operating state influence on output:                 Process image:
            PLC CPU stop            Acc. to substitute value strategy  Process data width  Depends on operating mode
            Fieldbus disruption     Acc. to substitute value strategy  LED indicators:
            S-bus (system bus) disruption  0 V status             SB: System bus status   LED (green/red/orange)
            Supply voltage under rated voltage                    F: Error status         LED (red)
            tolerance               0 V status                    0 ... 7: Input and output signal status  LED (yellow/red)
            Interruption of supply voltage  0 V status            U LS  + U A : Supply status  LED (green)
            Output operation        Non-latching                  Indicators              Non-latching
            Overload behavior       Automatic restart           General Specifications

                                                                Dimensions (mm) W x H x L  50 x 35.7 x 170
                                                                Weight                    389 g
   478   479   480   481   482   483   484   485   486   487   488