Page 483 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 483
6
481
System bus 1: RD+/TD+
Input Output 2: RD--/TD-- Block diagram of an input/output
3: TD--/RD--
4: TD+/RD+
5: GND Digital Input/Output Supply
Housing: Shield X1 ... X8
M12 B coded
M12 M12
2
3 Diagnostics sensor/actuator supply 4
Digital Inputs/Outputs 1: 24 V 1
X1 ... X8 3: 0 V U A Input 0 ... 7
10 nF 10 nF
Logic
Output 0 ...7
4
M12 A coded
4: In-/Output
2: n.c.
Input/Output Error
0 ... 7 F
10 nF 270 pF
Supply 1: 24 V U
Input Output 2: 24 V U LS
3: 0 V U A
4: 0 V U LS
A
Module
mount
M12 A coded
Technical Data Technical Data
Digital outputs: Counters: 6
No. of outputs 8 No. of counters 2
Connection type (2) M12 connectors, A coded, 4 poles Counter type Event/gate time counter, pulse duration
Wire connection 2- or 3-wire Counting/switching frequency 0 Hz ... 1 kHz
Output voltage ≤ U A System bus:
Output current (per channel) 0.5 A (max. 0.6 A), Connection type (3) M12 connectors, B coded, 5 poles, shielded
short-circuit/overload proof Standards and approvals:
(thermal disconnection) Conformity marking 1
Voltage drop against U A at 500 mA max. 0.2 V DC Korea Certification
Output current (module) max. 4 A r UL 508
Leakage current in OFF state typ. 5 μA Isolation:
Output circuit High-side switching Channel – Channel no
Information on actuator selection: U LS , U A , system bus 500 V DC each
Delay time hardware from "0" to "1" Configurable functions:
(0 – 90%) typ. 70 μs (resistive load) Operating mode (per module) DO-Module/DI-Module/DIO-Module/
Delay time hardware from "1" to "0" DIO + 1 counter/DIO + 2 counters
(0 – 90%) typ. 180 μs (resistive load) Counter Count direction, start/limit value switching
Rise time from "0" to "1" typ. 40 μs (resistive load) output, gate time
Fall time from "1" to "0" typ. 40 μs (resistive load) Input filter (per channel) 0.1/ 0.5/ 3 /15 /20 ms/ filter off
Cable length, unshielded ≤ 30 m Inversion (per channel) On/off
Reverse current (in case of recovery for Substitute value strategy (per channel) Switch substitute value/hold last value
voltages > U A ) ≤ 0,5 A (error: 1 channel) Substitute value (per channel) 0/1
Type of load Inductive, resistive loads and lamps Manual mode (per channel) On/off
Switching frequency Inductive load approx. 20 Hz Manual mode value (per channel) 0/1
Resistive load approx. 500 Hz Online simulation (per channel) Lock/unlock; simulation value: 0/1
Lamp load approx. 500 Hz Online simulation (per channel/module) Diagnostics
Parallel connection of 2 outputs for power boost I/O diagnostics:
for redundant actuation of a load I/O diagnostics (per channel) Overtemperature
Type of protective circuit External protection (e.g., recovery diodes) I/O diagnostics (per module) Sensor/Actuator supply short-circuit/
Output resistance < 0.4 Ω overload; Undervoltage (U LS + U A )
Operating state influence on output: Process image:
PLC CPU stop Acc. to substitute value strategy Process data width Depends on operating mode
Fieldbus disruption Acc. to substitute value strategy LED indicators:
S-bus (system bus) disruption 0 V status SB: System bus status LED (green/red/orange)
Supply voltage under rated voltage F: Error status LED (red)
tolerance 0 V status 0 ... 7: Input and output signal status LED (yellow/red)
Interruption of supply voltage 0 V status U LS + U A : Supply status LED (green)
Output operation Non-latching Indicators Non-latching
Overload behavior Automatic restart General Specifications
Dimensions (mm) W x H x L 50 x 35.7 x 170
Weight 389 g