Page 188 - Wagp_InterfaceElectronic_Volume4_2015_US.pdf
P. 188
857-423
3 JUMPFLEX Signal Conditioners
®
186 Signal Splitter with 2 configurable Current Outputs
Configuration via:
DIP switch
<_________ 96 mm/3.76 in _________> GND 1 1 2 IN OUT 1 5 OUT 1+
IN+
6 GND 2
8 GND 3
GND 4
_> OUT 2+ 3 4 OUT 2 POWER 7 Us+
____________
_>
6 mm/0.23 in
<_________ 94 mm/3.68 in _________>
Short description: Pack.
The 857-423 Signal Splitter converts standard signals and amplifies, filters and Description Item No. Unit
electrically isolates analog standard signals. ®
JUMPFLEX Signal Conditioner, for DIN 35 857-423 1
Signal Splitter with 2 configurable Current Outputs
Characteristics:
• Two configurable current outputs
• Calibrated scale switching
• Switchable max. operating frequency
• Safe 3-way isolation with 2.5kV test voltage to EN 61140
Technical Data Technical Data
Configuration: Environmental requirements:
Configuration DIP switch Ambient operating temperature -25 °C ... +70 °C
Input: Storage temperature -40 °C ... +85 °C
Input signal 0 ... 20 mA, 4 ... 20 mA, 0... 5 V, Safety and protection:
0 ... 10 V, 2 ... 10 V, 1 ... 5 V Test voltage (input/output/supply) 2.5 kV AC, 50 Hz, 1 min
(calibrated switchable) Connection and type of mounting:
®
Input resistance ≤ 50 Ω (In = mA) Wire connection CAGE CLAMP S
≥ 100 kΩ (In = V) Cross sections solid:
Output: 0.08 mm² ... 2.5 mm² / AWG 28 ... 14
Output signal 2 x 0(4) ... 20 mA fine-stranded:
(calibrated switchable) 0.34 mm² ... 2.5 mm² / AWG 22 ... 14
Load impedance 2 x 300Ω Strip lengths 9 ... 10 mm / 0.37 in
General specifications: Dimensions and weight:
24V DC Dimensions (mm) W x H x L 6 x 96 x 94
Nominal supply voltage V S
Supply voltage range 16.8 V ... 31.2 V Height from upper-edge of DIN 35 rail
Current consumption at 24 V DC ≤ 35 mA Weight 40.6 g
Max. operating frequency 100 Hz / 1 kHz Standards and approvals:
(switchable via DIP switch) Conformity marking 1
Response time (T 10-90 ) < 3.5 ms / < 300 μs r UL 508
Transmission error ≤ 0.1 % of the full scale value r ANSI/ISA 12.12.01 Class I, Div. 2, Grp. ABCD, T4
Temperature coefficient ≤ 0.01 % /K Shipbuilding g (pending)
Accessories see pages 226 … 236