Page 190 - Wagp_InterfaceElectronic_Volume4_2015_US.pdf
P. 190

857-450

   3    JUMPFLEX  Signal Conditioners
                     ®
  188   Loop-Powered Isolation Amplifier


                                                                                               Configuration via:








                                                                                                 DIP switch




                                                                         <_________ 96 mm/3.76 in _________>  U+  1  IN  OUT  5 Us+


                                                                                                 4-20 mA
                                                                                       U --
                                                                                                      6 OUT 1
                                                                                          2
                                                                                             U, I
                                                                                                      8 N.C.
                                                                                        I --
                                                                                          4
                                                                                 _>     I+  3    N.C.  7 N.C.
                                                                     ____________
                                                                             _>
                                                                            6 mm/0.23 in
                                                       <_________ 94 mm/3.68 in _________>
        Short description:                                                                                Pack.
        The 857-450 Loop-Powered Isolation Amplifier converts analog, unipolar and bipolar,   Description  Item No.  Unit
        standard signals. It is also designed to amplify, filter and electrically isolate standard
                                                                    ®
        analog signals.                                       JUMPFLEX  Signal Conditioner, for DIN 35 rail  857-450  1
                                                              Loop-Powered Isolation Amplifier
        Characteristics:
        • No additional supply voltage required
        • Zero/span adjustment
        • Analog, unipolar and bipolar, standard signals at input
        • Calibrated scale switching
        • Switchable max. operating frequency
        • Safe 2-way isolation with 2.5 kV test voltage to EN 61140
        Technical Data                                        Technical Data
        Configuration:                                        Environmental requirements:
          Configuration           DIP switch                    Ambient operating temperature  -25 °C ... +70 °C
        Input:                                                  Storage temperature    -40 °C ... +85 °C
          Input signal            Current:                    Safety and protection:
                                  ± 5 mA, 0 ... 5 mA,           Test voltage (input/output/supply)  2.5 kV AC, 50 Hz, 1 min.
                                  ± 10 mA, 0 ... 10 mA, 2 ... 10 mA,   Connection and type of mounting:
                                                                                                ®
                                  ± 20 mA, 0 ... 20 mA, 4 ... 20 mA    Wire connection  CAGE CLAMP  S
                                  Voltage:                      Cross sections         solid:
                                  ± 1 V, 0 … 1 V,                                      0.08 mm² ... 2.5 mm² / AWG 28 ... 12
                                  ± 5 V, 0 ... 5 V, 1 ... 5 V,                         fine-stranded:
                                  ± 10 V, 0 ... 10 V, 2 ... 10 V,                      0.34 mm² ... 2.5 mm² / AWG 22 ... 14
                                  ± 20 V, ± 2 V, 0 … 2 V        Strip lengths          9 ... 10 mm / 0.37 in
          Input resistance        approx. 1 MΩ (U input)      Dimensions and weight:
                                  approx. 50 Ω (I input)        Dimensions (mm) W x H x L  6 x 96 x 94
        Output:                                                                        Height from upper-edge of DIN 35 rail
          Output signal           4 ... 20 mA                   Weight                 37 g
          Load impedance          ≤ 600 Ω                     Standards and approvals:
          Overload capacity       30 V / 50 mA                  Conformity marking     1
        General specifications:                                 r UL 508
          Supply voltage          8 ... 30 V, power is derived from the output   Shipbuilding  g
                                  circuit                     Accessories              see pages 226 … 236
          Max. operating frequency  100 Hz / 30 Hz
                                  (switchable via DIP switch)
          Response time (T 10-90 )  3.5  ms
          Transmission error      ≤ 0.1 % of upper range value
          Temperature coefficient  ≤ 0.01 % /K
          Zero/span adjustment    ± 5 % of upper range value
   185   186   187   188   189   190   191   192   193   194   195