           JUMPFLEX  Signal Conditioners                                                                           3
           Passive Isolator, 2 Channels                                                                             191
















                                                                                                                    3
                                                                            <_________ 96 mm/3.76 in _________>  GND 1  1 2  IN 1  OUT 1  5 OUT 1+

                                                                                       IN 1+
                                                                                                        6 GND 2

                                                                                       IN 2+
                                                                                                        8 GND 4
                                                                                   _>  GND 3  3 4  IN 2  OUT 2  7 OUT 2+
                                                                       ____________
                                                                               _>
                                                                               6 mm/0.23 in
                                                         <_________ 94 mm/3.68 in _________>
           Short description:                                                                                Pack.
           The 2-channel passive isolator filters and electrically isolates 0(4)–20 mA ana-  Description  Item No.  Unit
           log standard signals, while drawing power for signal transmission from the input   JUMPFLEX  Signal Conditioner, for DIN 35 rail  857-452  1
                                                                      ®
           circuit. The connected sensor supplies the passive isolator with the required
           power, while powering the connected load.            Passive Isolator, 2 Channels
           Characteristics:
           • No additional supply voltage required
           • Safe 3-way isolation with 2.5kV test voltage to EN 61140


           Technical Data                                       Technical Data
           Input: *                                             Environmental requirements:
            Input signal            0(4) ... 20 mA                Ambient operating temperature  -25 °C ... +70 °C
            Responce current        < 200 μA                      Storage temperature     -40 °C ... +85 °C
            Voltage drop intput     < 2.0 V at 20 mA (output)   Connection and type of mounting:
                                                                                                  ®
            Max. input voltage      < 20 V                        Wire connection         CAGE CLAMP  S
            Max. input signal       40mA                          Cross sections          solid:
           Output: *                                                                      0.08 mm² ... 2.5 mm² / AWG 28 ... 14
            Output signal           0(4) ... 20 mA                                        fine-stranded:
            Load impedance          ≤ 600 Ω                                               0.34 mm² ... 2.5 mm² / AWG 22 ... 14
                                    (Temperature range restrictions may occur)  Strip lengths  9 ... 10 mm / 0.37 in
           General specifications:                              Dimensions and weight:
            Max. operating frequency  100 Hz                      Dimensions (mm) W x H x L  6 x 96 x 94
            Response time (T 10-90 )  < 3.5 ms                                            Height from upper-edge of DIN 35 rail
            Transmission error      ≤ 0.1 % of the full scale value  Weight               37.8 g
            Load error              ≤ 0.05 % of upper range value   Standards and approvals:
                                    per 100 Ω load                Conformity marking      1
            Temperature coefficient  ≤ 0.01 % /K                  r UL 508
                                                                  r ANSI/ISA 12.12.01     Class I, Div. 2, Grp. ABCD, T4
                                                                  Shipbuilding            g
                                                                Accessories               see pages 226 … 236















           ( * per channel)