Page 192 - Wagp_InterfaceElectronic_Volume4_2015_US.pdf
P. 192
857-451
3 JUMPFLEX Signal Conditioners
®
190 Passive Isolator, 1 Channel
<_________ 96 mm/3.76 in _________> GND 1 1 2 IN OUT 5 OUT+
IN+
6 GND 2
8 N.C.
N.C.
_> N.C. 3 4 7 N.C.
____________
_>
6 mm/0.23 in
<_________ 94 mm/3.68 in _________>
Short description: Pack.
The 1-channel passive isolator filters and electrically isolates 0(4)–20 mA ana- Description Item No. Unit
log standard signals, while drawing power for signal transmission from the input JUMPFLEX Signal Conditioner, for DIN 35 rail 857-451 1
®
circuit. The connected sensor supplies the passive isolator with the required
power, while powering the connected load. Passive Isolator, 1 Channel
Characteristics:
• No additional supply voltage required
• Safe 3-way isolation with 2.5kV test voltage to EN 61140
Technical Data Technical Data
Input: Environmental requirements:
Input signal 0(4) ... 20 mA Ambient operating temperature -25 °C ... +70 °C
Responce current < 200 μA Storage temperature -40 °C ... +85 °C
Voltage drop intput < 2.0 V at 20 mA (output) Connection and type of mounting:
®
Max. input voltage < 20 V Wire connection CAGE CLAMP S
Max. input signal 40mA Cross sections solid:
Output: 0.08 mm² ... 2.5 mm² / AWG 28 ... 14
Output signal 0(4) ... 20 mA fine-stranded:
Load impedance ≤ 600 Ω 0.34 mm² ... 2.5 mm² / AWG 22 ... 14
(Temperature range restrictions may occur) Strip lengths 9 ... 10 mm / 0.37 in
General specifications: Dimensions and weight:
Max. operating frequency 100 Hz Dimensions (mm) W x H x L 6 x 96 x 94
Response time (T 10-90 ) < 3.5 ms Height from upper-edge of DIN 35 rail
Transmission error ≤ 0.1 % of the full scale value Weight 33.8 g
Load error ≤ 0.05 % of upper range value Standards and approvals:
per 100 Ω load Conformity marking 1
Temperature coefficient ≤ 0.01 % /K r UL 508
r ANSI/ISA 12.12.01 Class I, Div. 2, Grp. ABCD, T4
Shipbuilding g
Accessories see pages 226 … 236