Page 22 - Gefran - Inverter system and power supply unit (ADV200 Drive family)
P. 22
22 Inverter System & Power Supply Unit
Asynchronous motor control
Overload Derating according to switching frequency (HD) Overload according to
output frequency
Sizes
ADV200 HD HD LD
150 % x In 180 % x In 110 % x In 2 kHz 4 kHz 6 kHz 8 kHz 10 kHz 12 kHz Heavy Duty Light Duty
ADV200 - 4 • Basic
(1’ each 5‘) (for 0,5’‘) (1’ each 5‘)
K1 HD K2 HD K3 HD K1 LD K2 LD
[a] [a] [a] [a] [a] [a] [a] [a] [a]
[%] [%] [Hz] [%] [Hz]
1007 3.7 4.5 4.7 2.5 2.5 2.5 2.5 2.1 1.8 100 3 4.8 100 3
1015 6.5 7.7 6.4 4.3 4.3 4.3 4.3 3.7 3 100 3 4.8 75 3
1022 8.7 10.4 8.4 5.8 5.8 4.9 4.1 3.7 3 100 3 4.8 75 3
1030 11.4 13.7 10.5 7.6 7.6 6.5 5.3 4.2 3 100 3 4.8 80 3
1040 14.3 17.1 14.3 9.5 9.5 8.1 6.7 5.7 4.75 100 3 4.8 100 3
2055 19.5 23.4 18.1 13 13 11.1 9.1 7.8 6.5 100 3 4.8 100 3
2075 24.7 29.7 25.3 16.5 16.5 14.0 11.6 9.9 8.25 100 3 4.8 75 3
2110 34.5 41.4 34.1 23 23 19.6 16.1 13.8 11.5 100 3 4.8 75 5
3150 46.5 55.8 41.8 31 31 26.4 21.7 18.6 15.5 100 5 8 75 7
3185 57 68.4 50.6 38 38 32.3 26.6 22.8 19 100 5 8 85 5
3220 69 82.8 68.2 46 46 39.1 32.2 27.6 23 100 3 4.8 80 5
4300 93 111.6 82.5 62 62 52.7 43.4 37.2 31 100 3 4.8 80 3
4370 113 135 95.7 75 75 63.8 52.5 45 37.5 100 3 4.8 80 3
4450 131 157 116 87 87 74 60.9 n.a. n.a. 100 3 4.8 80 3
5550 157 189 165 105 105 89 74 n.a. n.a. 100 3 4.8 85 5
5750 225 270 198 150 150 128 105 n.a. n.a. 100 5 8 85 5
5900 270 324 231 180 180 153 126 n.a. n.a. 100 5 8 85 5
61100 315 378 275 210 210 179 147 n.a. n.a. 100 3 4.8 100 3
61320 375 540 330 250 250 213 175 n.a. n.a. 100 3 4.8 100 3
71600 450 540 424 300 300 n.a. n.a. n.a. n.a. 100 3 4.8 80 3
72000 578 693 506 385 385 n.a. n.a. n.a. n.a. 100 3 4.8 100 3
72500 690 828 649 460 n.a. n.a. n.a. n.a. n.a. 100 3 4.8 75 5
73150 885 1062 715 590 n.a. n.a. n.a. n.a. n.a. 100 3 4.8 100 3
73550 975 1170 803 650 n.a. n.a. n.a. n.a. n.a. 90 5 7.5 90 5
400 kW 1095 1314 957 730 n.a. n.a. n.a. n.a. n.a. 100 3 4.8 100 3
500 kW 1305 1566 1232 870 n.a. n.a. n.a. n.a. n.a. 100 3 4.8 75 5
630 kW 1680 2016 1353 1120 n.a. n.a. n.a. n.a. n.a. 100 3 4.8 100 3
710 kW 1845 2214 1518 1230 n.a. n.a. n.a. n.a. n.a. 90 5 7.5 90 5
900 kW 2400 2880 1980 1600 n.a. n.a. n.a. n.a. n.a. 100 3 4.8 100 3
1 MW 2700 3240 2255 1900 n.a. n.a. n.a. n.a. n.a. 90 5 7.5 90 5
• In Light Duty mode the switching frequency is fixed at 4 kHz, and no derating factor is applied.
• If, in the Heavy Duty mode, the factory setting of Mod freq commutaz, (Switch freq. mode) PAR: 568 is changed from 0=Fixed to 1=Variable, the switching frequency is controlled by the temperature of the drive heat sink
and the output frequency. For further information see the ADV200 Functions and Parameters manual, menu 4.9.
Overload according to output frequency (Asynchronous motor control)
Overload HD Overload LD
200 120
190 k2
180
170 110 k1
160
150 100
I out [%] 140 k1 k2 I out [%]
130
120
110 90
100 80
90
80
70 70
0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 10
f [Hz] f [Hz]
_ _ Islow, .... Ifast; __ In _ _ Islow, .... Ifast; __ In