Page 21 - Gefran - Inverter system and power supply unit (ADV200 Drive family)
P. 21

Gefran S.p.A. - Drive & Motion Control Unit • www.gefran.com             21






                    Switching frequency
                           fsw                                      Reduction factor                                ADV200 - 4


            Sizes                            Kv          Kt   Kalt                     Kf (4)
           ADV200
                         Default  Higher  @400Vac  @460Vac     %
                                                and from
                                                 AFE200
                                         (1)      (1)    (2)   (3)   2 kHz  4 kHz   6 kHz  8 kHz  10 kHz  12 kHz    ADV200-DC

           1007         8      10, 12                          1.2     1      1      1       1     0.85    0.7

           1015         8      10, 12                          1.2     1      1      1       1     0.85    0.7
                                                                                                                    ADV200 - 6
           1022         4     6, 8, 10, 12                     1.2     1      1      0.85   0.7    0.55    0.4
           1030         4     6, 8, 10, 12                     1.2     1      1      0.85   0.7    0.55    0.4

           1040         4     6, 8, 10, 12                     1.2     1      1      0.85   0.7     0.6    0.5
           2055         4     6, 8, 10, 12                     1.2     1      1      0.85   0.7     0.6    0.5
           2075         4     6, 8, 10, 12                     1.2     1      1      0.85   0.7     0.6    0.5

           2110         4     6, 8, 10, 12                     1.2     1      1      0.85   0.7     0.6    0.5      ADV100
           3150         4     6, 8, 10, 12                     1.2     1      1      0.85   0.7     0.6    0.5
           3185         4     6, 8, 10, 12                     1.2     1      1      0.85   0.7     0.6    0.5

           3220         4     6, 8, 10, 12                     1.2     1      1      0.85   0.7     0.6    0.5
           4300         4     6, 8, 10, 12                     1.2     1      1      0.85   0.7     0.6    0.5      ADV80
                                               Tamb ≤ 30°C
           4370         4     6, 8, 10, 12  Tamb 40°C   = 1    1.2     1      1      0.85   0.7     0.6    0.5
                                         = 1    Tamb 40°C
           4450         4       6, 8             = 0,9         1.2     1      1      0.85   0.7     0       0
                                                         HD:
           5550         4       6, 8  from AFE200:       0.9   1.2     1      1      0.85   0.7     0       0
                                         Tamb
                                       ≤ 30°C =1  from AFE200:                                                      AFE200
           5750         4       6, 8             Tamb    LD:   1.2     1      1      0.85   0.7     0       0
                                      from AFE200:  ≤ 30°C =0.9  0.8
           5900         4       6, 8     Tamb                  1.2     1      1      0.85   0.7     0       0
                                       31 ... 40°C   from AFE200:
                                                 Tamb
           61100        4       6, 8     =0.9   31 ... 40°C    1.2     1      1      0.85   0.7     0       0
                                                 =0.81
                                                                                                                    FFE200
           61320        4       6, 8                           1.2     1      1      0.85   0.7     0       0
           71600        4        -                             1.2     1      1      0       0      0       0

           72000        4        -                             1.2     1      1      0       0      0       0
           72500        2        4                             1.2     1     0.85    0       0      0       0
                                                                                                                    SMB200
           73150        2        -                             1.2     1      0      0       0      0       0

           73550        2        -                             1.2     1      0      0       0      0       0
           400 kW      4   (5)   -                             1.2     1     1   (5)  0      0      0       0
           500 kW       2       4   (5)                        1.2     1    0.85   (5)  0    0      0       0
                                                                                                                    PROGRAM.
           630 kW       2        -                             1.2     1      0      0       0      0       0
           710 kW       2        -                             1.2     1      0      0       0      0       0

           900 kW       2        -                             1.2     1      0      0       0      0       0
           1 MW         2        -                             1.2     1      0      0       0      0       0

          (1) Kv :    Derating factor for mains voltage at 460Vac or AFE200 power supply.
          (2) Kt :    Derating factor for ambient temperature of 50°C (1% every °C over 40°C with HD and 2% every °C over 40°C with LD)
          (3) Kalt :    Derating factor for installation at altitudes above 1000 meters a.s.l. (up to a maximum of 2000 m). Value to be applied = 1.2% each 100 m increase above 1000 m.   APPENDIX
                 For example: Altitude 2000 m, Kalt = 1.2% * 10 = 12% derating; In derated = (100 - 12) % = 88 % In
          (4) Kf :    Derating factor for higher switching frequency
          (5)     from fw 6.03.
   16   17   18   19   20   21   22   23   24   25   26