18 Inverter System & Power Supply Unit
1.5 Choosing the Inverter
The combinations of motor power ratings and inverters listed in the table shows the use of motors in which the volt-
age rating is equal to that of the mains power.
For motors with different voltage ratings the inverter must be chosen according to the current rating of the motor.
The combinations listed in the table thus show the current that can be delivered by the drive during continuous op-
ADV200 - 4 • Basic
eration and overload conditions, according to the mains voltage.
The same engineering criteria apply for operations with additional derating factors:
• Kv Power supply voltage
• Kt Ambient temperature
• Kf Switching frequency
• Kalt Altitude of installation
1.6 Input Data
AC input current for
Input Input Overvoltage Undervoltage DC-Link Total harmonic continuous operation In
threshold
threshold
Sizes voltage frequency Capacity distortion Heavy Duty Light Duty
ADV200 Uln (Overvoltage) (Undervoltage) (150% overload) (110%overload)
[Vac] [Hz] [Vdc] [Vdc] [µF] [THD] % @ 400 Vac [Arms] @ 400 Vac [Arms]
1007 235 2.1 3.7
1015 235 3.7 4.9
1022 340 4.9 6.5
1030 340 6.5 8.1
1040 340 8.1 11.1
2055 680 11.1 14.0
2075 680 14.0 19.6
2110 830 19.6 26.4
3150 1500 26.4 32.3
3185 1500 32.3 39
3220 1500 39 53
4300 2350 53 64
4370 2800 64 74
4450 Three- 3400 40% Light Duty 74 100
phase
5550 mains 50/60 Hz, 820 380 4700 50% Heavy Duty 100 143
5750 380 Vac ± 2% 5600 143 171
-15% ... 500
5900 Vac +5% 6800 (at rated current) 171 200
61100 11200 200 238
61320 13600 238 285
71600 16800 300 350
72000 16800 350 420
72500 25200 420 580
73150 25200 580 640
73550 25200 640 710
400 kW 2 * 16800 665 800
500 kW 2 * 25200 800 1100
630 kW 2 * 25200 1100 1215
710 kW 2 * 25200 1215 1350
900 kW 3 * 25200 1650 1800
1 MW 3 * 25200 1800 2020