Page 57 - Gefran - Inverter system and power supply unit (ADV200 Drive family)
P. 57
Gefran Spa - Drive & Motion Control Unit • www.gefran.com 57
3.5 Choosing the Inverter
The combinations of motor power ratings and inverters listed in the table shows the use of motors in which the volt-
age rating is equal to that of the mains power. ADV200 - 4
For motors with different voltage ratings the inverter must be chosen according to the current rating of the motor.
The combinations listed in the table thus show the current that can be delivered by the drive during continuous op-
eration and overload conditions, according to the mains voltage.
The same engineering criteria apply for operations with additional derating factors:
ADV200-DC
• Kt Ambient temperature • Kf Switching frequency
• Kalt Altitude of installation • Kv Derating factor for power supply type
3.6 Input Data
Overvoltage Undervoltage AC input current ADV200 - 6
Input voltage threshold threshold DC-Link Total harmonic
Sizes Capacity distortion
ADV200-6 Uln (Overvoltage) (Undervoltage) Heavy Duty Light Duty
ADV100
[Vac] [Vdc] [Vdc] [µF] [THD] % @ 690 Vac [Arms] @ 690 Vac [Arms]
5750 4700 90 -
6900 Three-phase mains 6270 109 -
690 Vac ±10%,
61100 50/60 Hz, ± 2% 6270 129 -
ADV80
61320 6270 157 -
71600 11200 172 210
72000 11200 214 263
72500 11200 263 336
73150 11200 336 382 AFE200
40% Light duty,
73550 1192 676 (@690 Vac) 11200 50% Heavy duty (at 382 420
Three-phase mains rated current)
400 kW 22400 420 520
500 Vac -10%
...
500 kW 22400 533 651
690 Vac +10%,
630 kW 22400 665 755 FFE200
50/60 Hz ± 2%
710 kW 22400 756 843
900 kW 33600 1009 1180
SMB200
1 MW 33600 1180 1259
1.35 MW 44800 1375 1515
1.65 MW 56000 1680 1840
PROGRAM.
APPENDIX