86                                 Inverter System & Power Supply Unit





          5.7	 Output	Data


                    Inverter      Pn mot                          Maximum  Maximum
                    Output   (Recommended rated power   I2n         output   output
            Sizes  (IEC146 class  2),   of motor,   (Rated output current)  voltage  frequency   IGBT
           ADV80   150% overload   fsw = default)                    U2        f2     braking      Overload
      ...480V Power supply
      ADV200 - 4 • Basic
                                                                                       unit
                      60s
                             @400 Vac  @480 Vac  @400 Vac  @480 Vac
                     [kVA]                                           [V]      [Hz]
                               [kW]      [Hp]      [A]      [a]
             1004     0.8      0.37      0.5       1.1       1
             1005      1       0.55      0.75      1.5       1.4
             1007     1.4      0.75       1        2         1.8
                                                                                               Max. overload allowed:
             1015     2.6       1.5      1.5       3.7       3.2                                 ≡ 150% x I2n cl.2.
             2022     3.6       2.2       2        5.2       4.5                               I2N indicates the values
                                                                                       Internal   of the rated current for
             2030     4.7       3         4        6.8       5.9   0,94 x Uln          (with   the most common service
                                                                                       external
                                                                                                    profiles
             2040     6.4       4         5        9.2       7.6    (Uln =    500     resistor);   (ambient temperature =
                                                                    AC input           braking
             2055     8.2       5.5      7.5      11.8       9.7    voltage)         torque MAX   40°C, standard switching
                                                                                                   frequency).
                                                                                       150%
             2075     11.2      7.5      10       16.1      13.2
                                                                                               A similar criterion applies
             2110     15.9      11       15        23       20.7                                 for operations with
                                                                                              additional derating factors.
             3150     21.5      15       20        31       27.9

             3185     26.3     18.5      25        38       34.2

             3220     31.8      22       30        46       41.4


                          Switching frequency fsw                           Reduction factor
            Sizes
           ADV80        Default            Higher              Kt                 Kf                Kalt
      ADV80 • 400V
                         [KHz]             [KHz]               (1)                (2)               % (3)
             1004          8                 12                0.8         0.7 for higher fSW values  1.2
             1005          8                 12                0.8         0.7 for higher fSW values  1.2

             1007          8                 12                0.8         0.7 for higher fSW values  1.2
             1015          8                 12                0.8         0.7 for higher fSW values  1.2

             2022          8                 12                0.8         0.7 for higher fSW values  1.2

             2030          8                 12                0.8         0.7 for higher fSW values  1.2
             2040          8                 12                0.8         0.7 for higher fSW values  1.2
             2055          8                 12                0.8         0.7 for higher fSW values  1.2

             2075          8                 12                0.8         0.7 for higher fSW values  1.2

             2110          6                 8                 0.8         0.7 for higher fSW values  1.2
             3150          8                 12                0.8         0.7 for higher fSW values  1.2

             3185          8                 12                0.8         0.7 for higher fSW values  1.2
             3220          8                 12                0.8         0.7 for higher fSW values  1.2

          (1) Kt :    Derating factor with an ambient temperature of 50°C (1% every °C above 40°C)  (3) Kalt :    Derating factor for installation at altitudes above 1000 meters a.s.l.
          (2) Kf :    Derating factor for higher switching frequency      Value to be applied = 1.2% each 100 m increase above 1000 m.
                                                                     E.g.: Altitude 2000 m, Kalt = 1.2 % * 10 = 12% derating;
                                                                     In derated = (100 - 12) % = 88 % In