Page 82 - Gefran - Inverter system and power supply unit (ADV200 Drive family)
P. 82

82                                 Inverter System & Power Supply Unit





          5.3	 Standard	connections



                                         Braking
                                         Resistor
      ...480V Power supply
      ADV200 - 4 • Basic
                                       BR1   C    D
                                     U1/L1          U2/T1
                                     V1/L2          V2/T2       M
                                     W1/L3         W2/T3
                                     PE1             PE2
                    Run
                                     8 Dig Input 1
                    Reverse
                                     10 Dig Input 2
                    Ext Fault NO
                                     12 Dig Input 3
                    Jog
           Multi-Function  Fault Reset  14 Dig Input 4  9
             inputs                  16  Dig Input 5
                                                          Dig Output 1
                                     18  COM              50 Vdc / 40mA
                                                      11
                                     20  024V
                                     22  +24V
                                                          Dig Output 2
                                                      19
                                       Shield Ground      250 Vac / 1A
                                                      21   30 Vdc / 1A
                                     7  -10V(10mA)
                                     5 +10V(10mA)
                   Frequency  2 K   1 An Input 1
                   Reference
                                     2  S6  2  Voltage /
                                         1
                                             Current
                                     3 An Input 2
                                                                                        Standard connections and default drive
                                                      4  An Output 1 (Voltage)                     configuration sizes:
                                     13 Link+                                                Sizes ADV80-1... e ADV80-2...
                          Modbus                            FM 0...10 Vdc, 5 mA
                                                      2
                      Communications  15 Link-
                          RS-485                      6     FM 0...20 mA                  (Connections indicated for command
                                     17 Equ. Ref.                                        inputs are those most commonly-used
                                                        An Output 2 (Current)                   for PNP-type commands)
                                           Braking
                                          Resistor
      ADV80 • 400V
                                       BR    C1  C  D
                                     L1               U
                                     L2               V         M
                                     L3              W
                                     PE1             PE2
                    Run
                                     8 Dig Input 1
                    Reverse
                                     10 Dig Input 2
                    Ext Fault NO
                                     12 Dig Input 3
                    Jog
           Multi-Function  Fault Reset  14 Dig Input 4  9
             inputs                  16  Dig Input 5
                                                          Dig Output 1
                                     18  COM              50 Vdc / 40mA
                                     20  024V         11
                                     22  +24V
                                                          Dig Output 2
                                                      19
                                       Shield Ground      250 Vac / 1A
                                                      21   30 Vdc / 1A
                                     7  -10V(10mA)
                                     5 +10V(10mA)
                   Frequency  2 K   1 An Input 1
                   Reference
                                     2  S6  2  Voltage /
                                         1
                                             Current
                                     3 An Input 2
                                                                                           CStandard connections and default
                                                      4  An Output 1 (Voltage)                  drive configuration sizes:
                                     13 Link+                                                        Sizes ADV80-3..
                          Modbus                      2     FM 0...10 Vdc, 5 mA
                      Communications  15 Link-
                          RS-485                      6     FM 0...20 mA                  (Connections indicated for command
                                     17 Equ. Ref.                                        inputs are those most commonly-used
                                                        An Output 2 (Current)                   for PNP-type commands)
   77   78   79   80   81   82   83   84   85   86   87