Page 621 - Wago_Rail-MountedTerminalBlockSystems_Volume1_2015_US.pdf
P. 621

14


                                                                                                                    619
          Special Requirements               No special approval is required for ter-  The insulation between an intrinsically
          “Intrinsic safety Ex i”            minal blocks used as simple electrical   safe circuit and the chassis of an electri-
          The European Standard EN 60079-11 –  equipment for protection type “Ex i”, as   cal equipment or parts, which may be
          Classification VDE 0170, Part 7 – con-  they do not contain a voltage source and  grounded, has to withstand an effective
          tains special requirements for the design   precise information is available concern-  AC voltage corresponding to double the
          and testing of electrical equipment with   ing electrical data and temperature rise   value of the voltage of the intrinsically
          protection type – Intrinsic safety “i” – for  performance.            safe circuit or a minimum of at least
          use in hazardous areas.            The terminal blocks must be identifiable,   500V, depending on which value is high-
                                             for example by their type designation,   er.
          A circuit is designated as “intrinsically   and the following design requirements   The insulation between an intrinsically
          safe” when under normal operating con-  must also be upheld:          safe and a non-intrinsically safe circuit
          ditions and in the event of defined faulted  ●  The air distance between bare, con-  has to withstand an effective AC voltage
          conditions, no sparks and no thermal   ducting parts of terminal blocks of   of 2 x nominal value (U) +1 kV or a mini-
          effects can cause an ignition in a defined   different intrinsically safe circuits has   mum of 1.5 kV, whereby U represents the
          potentially explosive atmosphere.    to be equal or higher than the values   total of the effective voltages of the intrin-
                                               specified in the standard. In addition,   sically safe and the non-intrinsically safe
          A distinction is made here between:  the air distances between the terminal   circuit.
          ●  intrinsically safe electrical equipment   blocks must be so that the air distances  Short circuit between different intrinsically
            when all circuits are intrinsically safe   between bare, conducting parts of the  safe circuits could cause dangerous con-
            and                                connected external conductors is at   ditions. The insulation between these cir-
          ●  associated electrical equipment includ-  least 6 mm for one measurement. Each  cuits should withstand an effective volt-
            ing both intrinsically and non-intrinsical-  possible motion of metallic parts that   age of at least 500VAC or 2UAC where
            ly safe circuits, and being designed   are not rigidly fixed must be consid-  U is the total of the effective voltages for
            such that the non-intrinsically safe cir-  ered.                    the related circuits.
            cuits cannot affect the intrinsically safe  ●  When a possible connection has not   In accordance with the Electrical Installa-
            ones.                              been considered during safety analy-  tions Design Guideline DIN EN 60079-
                                               sis, the minimum clearance between   14 (VDE 0165-1), stranded and fine-
          Intrinsically safe electrical equipment and   grounded metallic or other conducting  stranded conductors used in intrinsically
          intrinsically safe parts of associated elec-  parts and the uninsulated conducting   safe circuits shall be protected against
          trical equipment are classified at protec-  parts of the conductors that are con-  splayed ends (e.g., via ferrules or pin ter-
          tion level “ia” or “ib.”             nected to the terminal blocks must be   minals) or by the type of terminal
          Products classified Ex “ia” shall not ignite   3 mm.                  blocks used. Tinning the conductor end
          when current is applied in the following   ●  Terminal block marking must be unique  alone is not permissible.
          cases:                               and clearly visible. If a color is used   Gastight tinned copper ferrules or tinned
          a)  During fault-free operation, with those   for this, the color must be light blue   copper pin terminals are recommended
            non-discreet faults present that result in   (similar to RAL 5015).  when connecting fine-stranded conduc-
            the most adverse condition.      Note also when using terminal blocks:  tors to terminal blocks in corrosive atmo-
          b)  During fault-free operation and with a   Terminal blocks used for intrinsically safe  spheres.
            discreet fault, plus those non-discreet   circuits must be isolated from those used
            faults that result in unfavorable condi-  in non-intrinsically safe circuits. This is
            tions.                           accomplished by several accepted meth-
          c)  During fault-free operation with two   ods. First, intrinsically safe circuits are
            discreet faults, plus those non-discreet   separated by at least 50mm of air space
            faults that result in the most adverse   from non-intrinsically safe circuits.
            conditions.
                                             Second, intrinsically safe circuits are
          Products classified Ex “ib” shall not ignite  housed in a separate enclosure. Third,
          when current is applied in the following   intrinsically safe terminal blocks are sepa-
          cases:                             rated from non-intrinsically safe terminal
          a)  During fault-free operation, with non-  blocks by either an insulated partition or
            discreet faults present that result in the  grounded metal partition. The partition
            most adverse condition;          size must allow for either 1.5mm or less                              14
          b)  During fault-free operation, with a   distance from the sides of the housing or
            discreet fault present, plus those non-  provide at least 50mm of creepage dis-
            discreet faults that result in the most   tance between the intrinsically and non-
            adverse condition.               intrinsically safe circuits in all directions.
   616   617   618   619   620   621   622   623   624   625   626