Page 617 - Wago_Rail-MountedTerminalBlockSystems_Volume1_2015_US.pdf
P. 617

14


                                                                                                                    615
          Approvals                          The marking of terminal blocks shall appear as follows in accordance with
                                             94/9/EC Ex Safety Guideline ATEX 100 a:
          Terminal blocks can be used in Zones I
          and II, provided that the terminal blocks
          are accommodated in an enclosure that                                      4      II   2   G     Ex e II
          has a minimum IP54 protection and an
          Ex e certification.                  Explosion prevention marking
          Terminal blocks are considered to be Ex   Group II (for equipment used in areas in which an explosive
          components, as they are a part of the   atmosphere might occur)
          equipment. Part certificates provided by
          Ex Certification Agencies serve as a
          basis for issuing the complete conformity   Category 2 (high safety, equipment used in areas [zones] in which a
          declaration for the unit.            potentially explosive atmosphere occurs only occasionally. Explosion
          In accordance with the Explosion Protec-  protection must continue to be provided even in the event of frequent
          tion Directive 94/9/EC (ATEX 100 a), an   equipment faults.)
          EC-type examination certificate based on
          ATEX 100 a is issued.                Gases
          In addition, an IEXEx Certificate may also   Explosion protection in Europe, type of protection “Increased Safety”,
          be obtained from an appropriate, recog-  Group II
          nized certification agency in accordance
          with the IECEx Certification Agreement   or
          that is accepted throughout Europe and                                     4      I     M 2      Ex e I
          also in countries such as Canada, China
          and Australia.                       Explosion prevention marking
          These certificates can also be viewed at:
          www.iecex.com.                       Group I (for equipment used in
                                               underground applications)

                                               Mining applications
                                               Explosion protection in Europe, type of protection “Increased Safety”,
                                               Group I









          Example of marking (rear):



          Series

          Manufacturer‘s name


          Nominal isolation voltage

          Type of protection


          Part certification no.

          Nominal cross section
          (solid, stranded or fine-stranded conductors)
                                                                                                                   14

          The embossed details on the terminal
          blocks show the manufacturer’s name, the
          series no., the type of protection Ex e II,
          the approval no., the approval data and
          the name of the test house.
   612   613   614   615   616   617   618   619   620   621   622