Page 618 - Wago_Rail-MountedTerminalBlockSystems_Volume1_2015_US.pdf
P. 618

14     – Continued –
        General Technical Information
  616 for Electrical Equipment in Hazardous Environments
        According to UL Standard 60079-7, ter-  EC-type examination certificates have   Tracking resistance with a CTI value of
        minal blocks for “Class I, Zone 1, Ex e II   been granted to all WAGO terminal   600 as per IEC 60112 and a constant
        hazardous locations” can be approved   blocks listed in this catalog.  operating temperature of 105°C/22°F
        for Ex applications.               The WAGO terminal blocks approved   in accordance with IEC 60216-1 and -2
        As a result of international harmonization  for the ignition protection type Ex e II   are provided.
        efforts, the UL certificate can be issued   are manufactured of flame resistant,   Factory part quality tests are performed
        on the basis of EN 60079-0 or      self-extinguishing Nylon 6.6. The same   on all CAGE CLAMP  rail-mounted termi-
                                                                                               ®
        EN 60079-7 standards, provided that   applies to the other terminal blocks in the  nal blocks with Ex e II approval to moni-
        the terminal blocks have also been   non explosion endangered area.   tor and ensure the quality features descri-
        approved in accordance with UL 1059                                   bed above.
        (ordinary location).
        If desired by the applicant, the product
        can simultaneously be approved in
        accordance with the Canadian Stan-
        dards E79-0-95 and E79-7-95 and
        released for use in Canada.
        The terminal blocks are marked with
        Y Cl. I, Zn. 1, AEx e II.
   613   614   615   616   617   618   619   620   621   622   623