                                                   Ignition Protection Categories

                              Symbol     Standard               Explanation            Application
                                                                                         Area
                               “o”     IEC 60079-6         Oil immersed apparatus:     Zone 1 + 2
                                       EN 60079-6   Electrical equipment or parts of such equipment
                                                              are immersed in oil.

                               “p”     IEC 60079-2          Pressurized enclosure:     Zone 1 + 2
                                       EN 60079-2    The ingress of the external (explosive) atmos-
                                                     phere into the electrical equipment housing is
                                                    prevented by maintaining a protective gas inter-
                                                     nally at a pressure above that of the external
                                                                atmosphere.
                               “q”     IEC 60079-5         Powder-filled apparatus:    Zone 1 + 2
                                       EN 60079-5   Filling the electrical equipment housing with fine
                                                    grain sand prevents the ignition of a surrounding
                                                    explosive atmosphere by an electric arc genera-
                                                              ted in the housing.

                               “d”     IEC 60079-1          Flameproof enclosure:      Zone 1 + 2
                                       EN 60079-1   The parts that could ignite an explosive atmos-
                                                     phere are encapsulated in a housing, which
                                                    will withstand the explosion pressure within the
                                                                 housing.
                               “e”     IEC 60079-7            Increased safety:        Zone 1 + 2
                                       EN 60079-7   Additional measures applied to achieve increa-
                                                    sed security against the possibility of excessive
                                                     temperatures and the occurrence of arcs or
                                                                  sparks.
                                “i”    IEC 60079-11           Intrinsic safety:        Zone 1 + 2
                                       EN 60079-11    Power circuit in which no sparks or thermal   following
                                                    effects can occur and cause the ignition of a cer-  special
                                                           tain explosive atmosphere.    testing
                                                                                         Zone 0

                               “n”     IEC 60079-15            Non-sparking:             Zone 2
                                       EN 60079-15   Electrical equipment of group II for use in areas
                                                    in which an explosive mixture of gas, vapor or
                                                    mist is unlikely to occur during normal operation
                                                      and, if it does, will be for a short period.
                               “m”     IEC 60079-18          Cast encapsulation:       Zone 1 + 2
                                       EN 60079-18  Dangerous electrical equipment is embedded in
                                                    a cast mass. This corresponds approximately to
                                                       the known special Ex s protection type.
                                       IEC 60079-25   Intrinsically safe electrical systems “i”:   Zone 1 + 2
                                       EN 60079-25  Assembly of interconnected electrical equipment   following
                                                    in which the circuits intended for use, as a whole   special
                                                    or in part, in hazardous environments are intrin-  testing
                                                    sically safe. It is documented accordingly in the   Zone 0
                                                              system description.

                                         IEC / TS             FISCO standard:
                                        60079-27    Electrical equipment for explosive gas atmosphe-
                                                    res – Part 27: Fieldbus intrinsically safe concept
                                                     (FISCO) and Fieldbus non-incendive concept
                                                                 (FNICO).