      CB trippings :
               The following are the cause known CB trippings for the year in The Division.
                                                                            Tree/
                             Monkey           Bird             Bad                     Sidings
               Year                                                         coal                   Total
                             Electrocuted  Electrocuted  Weather                       CB
                                                                            fallen
               2020-21
               ( As on            409               29             83          12         157       690
               31  OCT)
                  st
               Year          Monkey           Bird             Bad          Tree/co Sidings        Total
                             Electrocuted  Electrocuted  Weather  al                   CB
                                                                            fallen
               2021-22
               (  As  on          167               35             83          23         150       684
               31  Oct)
                 st
               Analysis of CB tripping:
                              CB Tripping                                      Monkey Electrocuted
                                                                               Bird Electrocuted
                                            25%                                Bad Weather
                          33%
                                                                               With Siding CB/BM
                                                5%
                                                                               Tree/Coal Fallen on Loco
                           3%                12%                               Roof
                                                                               Others
                                  22%
            The following preventive measures taken to reduce CB trippings:
           Sl.No.  Preventive Measures             Action Taken
           1.       Replacement               of  1030      No’s     Stay
                    Bracket/Stay      insulators  insulators,
                    with  composite  in  stone  856No.s          bracket
                    pelting areas.                 insulators changed
           2.       Nylon  mesh  provision  in  37 Nos. Of Portals.
                    portals  to  reduce  the
                    bird nest forming.
     	