Page 19 - GuardII+ Series 4208 Platform User Manual
P. 19

GuardII+ Operation



              4.  GuardII+ Operation


                        During normal asset operation, the sensors produce signals that are transmitted to the
                     GuardII+ via the Termination Boxes and cables.  The signals produced by the sensors are
                     analyzed for patterns in the measurement results.  Measurement data is analyzed, and the
                     monitor decides how the data will be handled.

                        Once fully configured, the monitor automatically collects and stores data from each of the
                     installed  monitoring  technologies,  produces  Alert  conditions  (if  configured),  and
                     collects/updates Remote I/O information.  However, if a particular feature is not used, then
                     the ability of the monitor to operate to its full capabilities may be compromised.  For example,
                     if the Alert Relay is not connected, or the Alert thresholds are not set, then the entire Alert
                     function will not work at all; the only way to tell if the data indicates a problem with the machine
                     being monitored is by downloading and then analyzing the data.

                                     NOTE:
                                     While each monitoring technology will have its own operational details,
                                     there  are  a  few  aspects  of  the  GuardII+  that  are  common  to  all
                                     technologies.

              4.1.  Online vs Offline

                        Once configured and online, GuardII+ does not require user intervention for any basic
                     functionality; it will run measurements, store them in the Archive, evaluate Alert levels, and
                     produce measurement results via Modbus.  This is the normal mode of operation.

                        While offline, GuardII+ stops collecting data.
                                     WARNING:
                                     The monitor MUST be online for normal operation.
                                     If GuardII+ is turned on, but has been offline for more than 24 hours, it will
                                     automatically go online unless a USB drive is left inserted into the panel
                                     (refer to Section 6.4.2 for details).


                        The  online status  is  shown  by  the  Online  indicators  on the front  panel and  inside  the
                     monitor; the indicators are green when GuardII+ is online.














                                       Figure 4-1 GuardII+ Front Panel Online Indicator







                                                            13