GuardII+ Operation



              4.5.3.  Alert State

                        When GuardII+ enters the Alert state, the following occurs:
                        •  The Alert Relay is activated (as it is configured in IAM).

                        •  Depending on the specific monitoring technology, the measurement that caused the
                            Alert may have an additional effect such as saving the measurement in the Archive.

                        •  The front panel Alert indicator turns amber.  Refer to Section 8 for full details on the
                            indicator functions.















                                             Figure 4-3 Front Panel Alert Indicator
                        •  The Alert indicators on the inside of the monitor are updated to reflect the Alert status.
                            Refer to Section 8 for full details on the indicator functions.















                                              Figure 4-4 Internal Alert Indicators
                        •  The Alert Modbus data is updated.

              4.5.4.  Stale Alert State
                        After an Alert has been triggered, measurement results may sometimes change back to a
                     non-Alerted state.  When this occurs, the monitor changes the Alert status to a ‘stale’ state,
                     meaning that there was an Alert, but it is no longer occurring.
                        •  In a stale Alert state, the Alert indicator on the front panel will start to blink amber.

                        •  The Alert Relay will de-activate.
                        •  The Alert Modbus data is updated.