P. 20

GuardII+ Operation


















                                              Figure 4-2 Internal Online Indicator

              4.2.  Measurement Cycle

                        While  the  GuardII+  is  online,  it  is  constantly  cycling  through  the  different  monitoring
                     technologies and updating the various support systems required by the technologies.

                            •  Each monitoring technology follows its own measurement cycle.  The duration of
                                a  measurement  cycle  will  depend  on  the  technology  (refer  to  the  specific
                                monitoring technology User Manuals).
                            •  Archiving and Alerts are handled by each monitoring technology independently.
                                The exact rules for processing these functions depend on the specific monitoring
                                technology (refer to the specific monitoring technology User Manuals).
                            •  Operating Condition data is imported and updated after every measurement if the
                                Modbus input or the Remote I/O is configured.
                            •  Modbus slave data is updated after every measurement cycle of any technology is
                                completed.    For  example,  when the  PD measurement  is finished, then  the  PD
                                Modbus data is updated.  Similarly, when a Rotor Flux measurement is completed,
                                then the Flux Modbus data is updated.
                            •  GuardII+ diagnostic information is updated every 30 minutes.

              4.3.  Operating Conditions

                        Measurement results can be affected by the current Operating Conditions of the asset
                     being monitored such as voltage, active power/load, temperature, humidity, etc.  The benefit
                     of acquiring Operating Condition data is that it provides context to the data collected.  For
                     example, if two measurements show significantly different results, it may not be a cause for
                     concern,  but  because  the  Operating  Conditions  were  different.    By  acquiring  and  storing
                     Operating Condition data with the data, results at consistent Operating Conditions can be
                     analyzed, which provides a more meaningful analysis.

                        Different monitoring technologies  benefit from  different  Operating  Condition  data.   For
                     example, some PD measurement results can be significantly affected by the ambient humidity;
                     but  for  endwinding  vibration  (EV)  measurement  results,  the  ambient  humidity  is  not  a
                     significant factor.
                        GuardII+ provides three main ways of acquiring Operating Condition data:
                        •  The monitor can read data from a plant control system using Modbus over TCP/IP.



                                                            14