                          1500 – MECHANICAL




                             HEATING/AIR CONDITIONING for Office building & Plant offices

                             Provide gas fired, forced air, heating and cooling, consisting of a split-system with a
                             suspended furnace and outside condensing unit. Completely separate systems to be provided
                             for the upper and lower office areas. Split systems to be complete with adequately sized,
                             insulated supply ductwork and manually adjustable ceiling mounted diffusers. Suspended
                             ceiling space to be used for cold air return, with adequate and suitably located ceiling
                             mounted return air grilles. Fire dampers required at all penetrations of a rated assembly.
                             System to be controlled by a programmable combination heat/cool thermostat.


                                    Heating design criteria
                                    Maintain an inside temperature of 68 degrees Fahrenheit at an outside temperature of
                                    –20 degrees Fahrenheit


                                    Cooling design criteria
                                    Maintain an inside differential of  -12 degrees maximum to outside temperature.
                                    E.I.:  outside at +90 degrees Fahrenheit = inside at maximum +78 degrees
                                    Fahrenheit.


                                    Accessories
                                    Provide adequate bases, aesthetic screening and suspension supports for all
                                    equipment and appurtenances. All exposed refrigeration lines, wiring and
                                    condensation piping to be properly terminated and protected in accordance with
                                    standard trade practices, governing code and local authority.