Chapter 2 SALES 83
Presentation Booklet: Sample Proposal Outline Specifications
Outline Specifications
l�L for
CON5TRUCTION ACME Manufacturing
YOUR CO NPLET E DES!G N-8U!LDER
1500 – MECHANICAL
HEATING Plant
Provide a combination of gas fired suspended unit heaters and tubular radiant heating units.
Unit heaters to provide recovery heating for overhead door opening occurrences, with the
radiant heating units supplying the general heating needs of the Plant area. Size, location,
mounting height and number of heating units required to be based on the following design
criteria. Unit heaters to be vented through roof with proper roof jacks and radiant heaters
vented through exterior wall with proper sleeve assemblies.
Heating Design Criteria for Plant
Maintain an inside temperature of +68 degrees Fahrenheit at an outside temperature
of –20 degrees Fahrenheit
Accessories
Provide adequate suspension supports from the roof structure for all equipment and
appurtenances. All exposed supply piping, wiring and venting to be properly
terminated and protected in accordance with standard trade practices, required
distance clearances, governing code and local authority.