                           1600 - ELECTRICAL

                               Incoming Service

                               Provide 220 volt, single phase, 600 amp, underground incoming electrical service. Service
                               panels, splitter, meter base and main disconnect to be located on interior face of tool room
                               exterior wall in Plant area. Provide separate sub-panels with disconnect for Plant area and
                               upper and lower levels of the office building.


                               Lighting

                                      General/Private Offices/Washrooms
                                      Recessed florescent fixtures, 2.0 ft. x 4.0 (4 tube) to provide lighting level of? Foot-
                                      candles.

                                      Plant Offices/Washrooms
                                      Surface mounted, wrap florescent fixtures, 1.0 ft. x 4.0 ft. (2 tube) to provide lighting
                                      level of? Foot-candles.

                                      Plant
                                      Strip fluorescent fixtures two- (2) tube x 8.0 ft. suspended from structural roof
                                      system to provide a lighting level of? Foot-candles.

                                      Emergency
                                      Provide separate outlet and connected wall mounted double head battery emergency
                                      units to general offices (2), stairwells (2) and plant area (2). Provide standard wall
                                      mounted exit light fixtures at all main exit points in office and plant (7).

                                      Exterior
                                      Provide 250 watt; wall mounted metal halide fixtures over all exit doors (4) at Plant
                                      and upper portion of wall at corner (2) of Plant facing trucking yard. Provide
                                      recessed 100-watt pot lights (total 8) to soffit at both Office main entrance canopies.
                                      Provide parking lot lighting utilizing twin head fixtures on metal poles set on
                                      concrete bases to provide code-required level of yard illumination.