               1.4  Overview


               The primary objective of this fire strategy review is to identify how an acceptable level of fire

               safety may be achieved commensurate with the Requirements of the Building Regulations
               2010. The Buildings Regulations 2010 is the Statutory Instrument which seeks to ensure the
               policies set out in the Building Act 1984 are implemented. The requirements of the Building

               Regulations 2010 may be met in one of two ways, compliance with an accepted design code
               or through a fire engineered approach.


               In this instance the primary design code used is Approved Document B (ADB).

               The Building Regulations outline 5 Functional Requirements of Fire Safety, as detailed
               below:


                   •   B1 – Means of Warning and Escape,

                   •   B2 – Internal Fire Spread (Linings),

                   •   B3 – Internal Fire Spread (Structure),


                   •   B4 – External Fire Spread, and

                   •   B5 – Access and Facilities for the Fire Service.


               This report aims to address each of the Functional Requirements above and provides
               comment on the ongoing Fire Safety Management required within retail premises.

               Under Regulation 3 of the Building Regulations 2010, the term ‘Material Alteration’ is defined

               by reference to a list of ‘relevant requirements’ of Schedule 1 of the Building Regulations.
               That list includes the requirements of Parts B1, B3, B4 and B5. This means that an alteration

               which, at any stage of work, results in a building being less satisfactory than it was before in
               relation to compliance with Parts B1, B3, B4 and B5 is a material alteration, and is therefore
               controlled by Regulation 4 as it is classified as ‘building work’.

               1.5  B1 – Means of Warning and Escape



               1.5.1      Fire alarm and detection system


               All stores are to be provided with an automatic fire alarm and detection system designed and
               installed to not less than Category L3 standard, in accordance with BS5839-1. It is noted that

               this is an enhancement above the Category M alarm system, required by ADB for such
               premises. This level of automatic system should provide coverage to ground and basements



              Document Classification     Final    Document Ref:   3.1-RCS-RHSE-(110)-263   Version   1.1