Reference Guide                                                         Fire Strategy



               The following table outlines the exit capacity of exits from a given width:


                             Maximum number of persons             Minimum width (mm)

                                          60                                750


                                          110                               850

                                          220                              1,050


                                    More than 220                     5mm per person

               Note: the above requirements do not take account any further limitations stipulated in

               Approved Document M: Access to and Use of Buildings.

               1.5.4      Travel Distances


               Approved Document B specifies the following maximum travel distances for a building of
               Shop and Commercial use:

                                  Maximum travel distance where escape is possible in


                                                 One direction only (m)  More than one direction (m)

                 Shop and Commercial                      18m                         45m


                 Office                                   18                           45

                 Storage (Normal Hazard)                  25                           45


                 Storage (Higher Hazard)                  12                           25

                 Place of Special Fire Hazard              9                           18

                 Plant Room                                9                           35


               Travel distance should be measured from the most remote part of the floorplate to a place of
               relative safety, which may be a final exit, a protected stair enclosure or a compartment

               boundary. Travel distances should take account of actual escape routes and therefore
               cannot be measured over fixtures or furniture. Where the internal layout of fittings, partitions

               etc. is not known, direct distances may be taken as 2/3rds the prescribed limit specified in
               the table above.