GENERAL ELECTRICAL SPECIFICATION
Version 2014-2
Where additional discrete kitchen equipment is required as part of the kitchen fit-out the Contractor
shall provide electrical circuits as directed by the H&K equipment schedule or in the absence of
complete information allow for the following, unless otherwise directed by the Project Manager.
OTHER MISCELLANEOUS DISCRETE KITCHEN EQUIPMENT
Item Electrical Requirements
Description Location Circuit
Protection Connector Cable size
Apple Pie Wall mounted socket fixed Single pole1 x 16A SP&N IP67 wall 3-core
2
200mm below ceiling level. 16A RCBO mounted ceeform4mm YY
socket, part no 1720.
Ice machine Wall mounted socket fixed Single pole1 x 16A SP&N IP67 wall 3-core
2
200mm below ceiling level. 16A RCBO mounted ceeform4mm YY
socket, part no 1720.
Egg cooker Wall mounted socket fixed Single pole1 x 16A SP&N IP67 wall 3-core
2
200mm below ceiling level. 16A RCBO mounted ceeform4mm YY
socket, part no 1720.
Orange Juice Wall mounted socket fixed Single pole1 x 16A SP&N IP67 wall 3-core
2
machine 200mm below ceiling level. 16A RCBO mounted ceeform4mm YY
socket, part no 1720.
Hot Chocolate Wall mounted socket fixed Single pole1 x 16A SP&N IP67 wall 3-core
2
machine 200mm below ceiling level. 16A RCBO mounted ceeform4mm YY
socket, part no 1720.
All sockets and plugs as manufactured by Mennekes Electric Ltd., unless otherwise directed.