Page 94 - RotF - Electrical Specification_Neat
P. 94

GENERAL ELECTRICAL SPECIFICATION
                                 Version 2014-2



               A.1       KITCHEN EQUIPMENT


               The Electrical Contractor shall provide power supplies as per the H&K equipment schedules, in the
               absence of complete information allow for the following, unless otherwise indicated by or as
               directed by the Project Manager:

               ISLAND PREP TABLE

               Item                                      Electrical Requirements
               Description    Location                   Circuit
                                                         Protection     Connector               Cable size
                              Located above the ceiling 4-pole      63A1 x 63A TP&N in-line  5-core
                                                                                                     2
                              over the assembly table Type C MCB IP67 ceeform socket, 25mm  YY
                              (OAT)                      & RCD          part no 14212
                              Located above the ceiling 2 x 4-pole  2 x 32A TP&N in-line  5-core
                                                                                                    2
                              over each end of the centre  32A Type C IP67 ceeform sockets,  6mm  YY
                              section, allow sufficient MCBs            par
                                                                         &t no 3907
                              flex length to relocate to RCDs
                              phase 2 positions.
               MFY Pre table   Located above the ceiling, 4-pole    63A1 x 63A TP&N in-line  5-core
               (Phase 1)                                                                             2
                              63A TP&N socket to be Type C MCB IP67 ceeform socket 25mm  YY
                              positioned to suit phase 2 & RCD          (part no 14212) with
                              requirements;        between              63A TP&N IP67 in-line
                              toasters and microwave                    plug (part no 13212)
                              table, flex to extend 32A                 and short cable to 32A
                              TP&N socket to suit phase                 TP&N        IP67 -line  in
                              1 requirement.                            ceeform socket, part no
                                                                        3907
                              Retained from phase 1 4-pole          63A1 x 63A TP&N IP67 5-core
                                                                                                     2
                              installation               Type C MCB Ceeform socket, part no  25mm  YY
                                                         & RCD          14212.

                              Retained from phase 1 2 x 4-pole  2 x 32A TP&N IP67 5-core
                                                                                                    2
               MFY Pre table   installation, relocated to 32A Type C Ceeform sockets, part  6mm  YY
                                                                         &
               (Phase 2)      suit phase 2 equipment MCBs               no 3907.
                              arrangements               RCDs
                              Retain 63A outlet from 4-pole         63A1 x 63A TP&N IP67 5-core
                                                                                                     2
                              phase 1, remove 63A plug Type C MCB Ceeform socket, part no  25mm  YY
                              and flex to 32A socket, & RCD             14212
                              retain for future use.