Page 95 - RotF - Electrical Specification_Neat
P. 95
GENERAL ELECTRICAL SPECIFICATION
Version 2014-2
CENTER ISLAND BEVERAGE CELL
Item Electrical Requirements
Description Location Circuit
Protection Connector Cable size
Shake In-line socket and flex to 4-pole 32A1 x 32A TP&N IP67 in- 5-core
2
Machine drop down chase, final Type C MCB line ceeform socket 6mm YY
location to suit & R siteCD (part no 3907)
conditions
McFlurry In-line socket and flex to Single pole1 x 16A SP&N IP67 in- 3-core
2
drop down chase, final 16A RCBO line ceeform socket 4mm YY
location to suit site (part no 3860)
conditions
In-line socket and flex to Single pole1 x 16A SP&N IP67 in- 3-core
2
drop down chase, final 16A RCBO line ceeform socket 4mm YY
Adande chiller
location to suit site (part no 3860)
conditions
Wall mounted socket fixed Single pole1 x 16A SP&N IP67 wall 3-core
Multi-deck 1200mm above finished 16A RCBO mounted ceeform4mm YY
2
chiller
floor level. socket, part no 1720
Wall mounted socket fixed Single pole1 x 16A SP&N IP67 wall 3-core
Blended Ice 1200mm above finished 16A RCBO mounted ceeform4mm YY
2
machine
floor level. socket, part no 1720
Alternatively: Located above the ceiling 4-pole 63A1 x 63A TP&N IP67 5-core
2
Drinks table to suit the position of the Type C MCB Ceeform socket, part no 25mm YY
chase for;beverage cell chase. & RCD 14212
Blended ice,
McFlurry,
Adande
chiller, Shake
machine and
multi-deck
chiller
Beverage cell Located above the ceiling 4-pole 63A1 x 63A TP&N IP67 5-core
2
chase for;to suit the position of the Type C MCB Ceeform socket, part no 25mm YY
Coffee beverage cell chase. & RCD 14212
machine, hot
choc and
drinks
McDonalds Restaurants Ltd