GENERAL ELECTRICAL SPECIFICATION
                                 Version 2014-2



               Where additional main kitchen equipment is required as part of the kitchen fit-out the Contractor

               shall provide electrical circuits as directed by the H&K equipment schedule or in the absence of
               complete information allow for the following, unless otherwise directed by the Project Manager.
               Item                                      Electrical Requirements
               Description    Location                   Circuit        Connector               Cable size

                                                         Protection
               2, 4 or 5 bay Located above the ceiling 4 pole type C  1 x 125A TP&N IP67 in- 5-core
                                                                                                     2
               fry station    above the identified chase.   125 MCB and  line ceeform socket, 50mm  YY
                                                         RCD            part no 14225
               2, 3 or 4 bay Located above the ceiling 4 pole type C  1 x 125A TP&N IP67 in- 5-core
                                                                                                     2
               chicken Fillet above the identified chase.   125 MCB and  line ceeform socket, 50mm  YY
               station                                   RCD            part no 14225
               2, 4 or 5 Located above the ceiling 4 pole type C  1 x 125A TP&N IP67 in- 5-core
                                                                                                     2
               platen        grillabove the identified chase.   125 MCB and  line ceeform socket, 50mm  YY
               station                                   RCD            part no 14225
               Mobile/        Located above the ceiling  4-pole     32A1 x 32A TP&N IP67 in- 5-core
                                                                                                    2
               temporary      above the identified chase.   Type C MCB line ceeform socket 6mm  YY
               equipment                                 & RCD          (part no 3907)
               station
               Toaster Box    In-line     socket     hanging4-pole  32A1 x 32A TP&N IP67 in- 5-core
                                                                                                    2
                              below the ceiling at the Type C MCB line ceeform socket 6mm   YY,
                              identified           connection& RCD      (part no 3907)          with black
                              point, complete with high                                         outer
                              strength cable restrainer                                         sheath
                              positioned so that the
                              force exerted by the cable
                              does not interfere with the
                              integrity    of     the     false
                              ceiling.