GENERAL ELECTRICAL SPECIFICATION
Version 2014-2
A.2 ANCILLARY EQUIPMENT
Where the existing distribution to the kitchen in general is determined to be un-safe or otherwise
requires replacement the Contractor should include for the following miscellaneous supplies in the
absence of complete information, unless otherwise directed by the Project manager:
OTHER MISCELLANEOUS COMPONENTS
Item Electrical Requirements
Description Location Circuit
Protection Connector Cable size
Walk-in Wall mounted isolator20A -pole Wall mounted TP&N 5-core
3
2
freezer fixed 200mm below ceiling Type D MCB 20A, IP66 rotary isolator 6mm YY
level.
Walk-in chiller Wall mounted isolatorSingle poleWall mounted SP&N 3-core
2
fixed 200mm below ceiling 20A Type D 20A, IP66 rotary isolator 4mm YY
level. MCB
Washing Wall mounted socket fixed Single pole1 x MK Masterseal IP66 3-core
2
Machine 1200mm above finished 20A RCBO switched twin socket 4mm YY
floor level. outlet
Single poleWall mounted 20A, IP66 3-core
2
Drinks Wall mounted devices fixed 20A type C rotary isolator 4mm YY
MCB
Multiplex unit 1200mm above finished
(Whitelenge floor level. Single pole1 x MK Masterseal IP66 3-core
2
equipment) 20A RCBO switched twin socket 4mm YY
outlet
Hand dryer Wall mounted ed fusSingle pole1 x MK Metalclad 3-core
2
connection unit fixed20A RCBO switched FCU 4mm YY
2200mm above finished
floor level.
Insectocutor Wall mounted fusedSingle pole1 x MK Metalclad 3-core
2
connection unit fixed20A Type C switched FCU 4mm YY
200mm below ceiling level. MCB
Booth heater Wall mounted fusedSingle pole1 x MK Metalclad 3-core
2
connection unit fixed20A type C switched FCU 4mm YY
200mm below ceiling level. MCB
All circuit protection devices by Schneider Electric, their Acti 9 Isobar iC60H and iC120 ranges.
All cables will have an LSF outer sheath unless otherwise directed.