LOFT LIFE CONVERSIONS – GENERAL SPECIFICATION
DORMER ROOF
High quality 20 year Guarantee, on 18mm external quality plywood, on firings @ 1:40 fall. All onto flat roof joists
as specified on plan. 100mm Celotex insulation between joists. Lined internally with plasterboard.
DOUBLE GLAZED ROOF WINDOWS
Openings to be fully trimmed using 2x100x50 SC3 rafters and installed to manufacturers recommendations. All
windows to have inner pane of min 4mm toughened glass to give AA rating where below 800mm.
STAIRCASE
All risers/going to be uniform throughout flight. Max 42* pitch. Min 16mm nosing. winders to have equal angles
on plan and min.50mm around newel posts. Min. headroom as per part K (min. 1800-2000mm depending on
position).
GUARDING (SPINDLES)
Balustrade to be min 900mm above nosing line of staircase/landing. No part of balustrade to allow passage of
100mm dia sphere to pass.
DOORS
All doors leading to habitable room off existing stairwell to be fitted 1/2 hour fire resistant to building
regulation requirements / intumescent coating to existing doors.
VENTILATION
All rooms to have openable windows - 1/20 of floor area with part min. 1750mm above floor level. Areas to have
background ventilation of min. 8000mm. 25mm continuous strip ventilation to eaves, circular/square vents to
existing eaves@400cc. Tiles/ridge vents to apex at 1500 c/c to give 5mm continuous vent. All vents to have insect
mesh.