WALL CONSTRUCTION



              R607.5.2.1  Panel  anchor  restraints.  Panel  anchors  R608.1.1  Interior  construction.  These  provisions  are
              shall be spaced not greater than 16 inches (406 mm) on  based on the assumption that interior walls and partitions,
              center in both jambs and across the head. Panel anchors  both  load-bearing  and  nonload-bearing,  floors  and  roof/
              shall be embedded not less than 12 inches (305 mm)  ceiling assemblies are constructed of light-framed construc-
              and shall be provided with two fasteners so as to resist  tion complying  with the  limitations  of  this  code and the
              the loads specified in Section R607.5.2.           additional limitations of Section R608.2. Design and con-
                                                                 struction of light-framed assemblies shall be in accordance
              R607.5.2.2  Channel-type  restraints.  Glass  unit
              masonry panels shall be recessed not less than 1 inch (25  with the applicable provisions of this code. Where second-
              mm) within channels and chases. Channel-type restraints  story exterior walls are of light-framed construction, they
              shall be oversized to accommodate expansion material in  shall be designed and constructed as required by this code.
              the opening, packing and sealant between the framing  Aspects  of  concrete  construction  not  specifically
              restraints, and the glass unit masonry perimeter units.  addressed by this code, including interior concrete walls,
         R607.6 Sills. Before the bedding of glass units, the sill area  shall comply with ACI 318.
         shall be covered with a water-base asphaltic emulsion coat-  R608.1.2 Other concrete walls. Exterior concrete walls
         ing. The coating shall be not less than  /  inch (3 mm) thick.  constructed  in  accordance  with  this  code  shall  comply
                                        1
                                         8
         R607.7 Expansion joints. Glass unit masonry panels shall be  with  the  shapes  and  minimum  concrete  cross-sectional
         provided with expansion joints along the top and sides at all  dimensions of Table R608.3. Other types of forming sys-
         structural supports. Expansion joints shall be not less than  / 8  tems  resulting  in  concrete  walls  not  in  compliance  with
                                                        3
         inch (10 mm) in thickness and shall have sufficient thickness  this section shall be designed in accordance with ACI 318.
         to  accommodate  displacements  of  the  supporting  structure.  R608.2 Applicability limits. The provisions of this section
         Expansion  joints  shall  be  entirely  free  of  mortar  and  other  shall apply to the construction of exterior concrete walls for
         debris and shall be filled with resilient material.  buildings not greater than 60 feet (18 288 mm) in plan dimen-
         R607.8 Mortar. Glass unit masonry shall be laid with Type S  sions, floors with clear spans not greater than 32 feet (9754
         or N mortar. Mortar shall not be retempered after initial set.  mm) and roofs with clear spans not greater than 40 feet (12
         Mortar unused within 1 /  hours after initial mixing shall be  192 mm). Buildings shall not exceed 35 feet (10 668 mm) in
                            1
                             2
         discarded.                                           mean roof height or two stories in height above grade. Floor/
                                                              ceiling dead loads shall not exceed 10 pounds per square foot
         R607.9  Reinforcement.  Glass  unit  masonry  panels  shall  (479 Pa), roof/ceiling dead loads shall not exceed 15 pounds
         have horizontal joint reinforcement spaced not greater than  per square foot (718 Pa) and attic live loads shall not exceed
         16 inches (406 mm) on center located in the mortar bed joint.  20 pounds per square foot (958 Pa). Roof overhangs shall not
         Horizontal joint reinforcement shall extend the entire length  exceed 2 feet (610 mm) of horizontal projection beyond the
         of the panel but shall not extend across expansion joints. Lon-  exterior  wall  and  the  dead  load  of  the  overhangs  shall  not
         gitudinal wires  shall be lapped not less  than  6  inches  (152  exceed 8 pounds per square foot (383 Pa).
         mm) at splices. Joint reinforcement shall be placed in the bed
         joint  immediately  below  and  above  openings  in  the  panel.  Walls constructed in accordance with the provisions of this
         The reinforcement shall have not less than two parallel longi-  section shall be limited to buildings subjected to a maximum
         tudinal wires of size W1.7 or greater, and have welded cross  design wind speed of 160 mph (72 m/s) Exposure B, 136 mph
         wires of size W1.7 or greater.                       (61  m/s)  Exposure  C  and  125  mph  (56  m/s)  Exposure  D.
                                                              Walls constructed in accordance with the provisions of this
         R607.10 Placement. Glass units shall be placed so head and  section  shall  be  limited  to  detached  one-  and  two-family
         bed  joints  are  filled  solidly.  Mortar  shall  not  be  furrowed.  dwellings and townhouses assigned to Seismic Design Cate-
                                                 1
         Head and bed joints of glass unit masonry shall be  / inch (6.4
                                                  4
         mm) thick, except that vertical joint thickness of radial panels  gory  A  or  B,  and  detached  one-  and  two-family  dwellings
                                                              assigned to Seismic Design Category C.
                                                  5
                          1
         shall be not less than  /  inch (3 mm) or greater than  /  inch (16
                           8
                                                   8
                                                    1
         mm). The bed joint thickness tolerance shall be minus  /  inch  Buildings that are not within the scope of this section shall
                                                     16
                         1
         (1.6 mm) and plus  /  inch (3 mm). The head joint thickness  be designed in accordance with PCA 100 or ACI 318.
                          8
                                   1
         tolerance shall be plus or minus  / inch (3 mm).     R608.3 Concrete wall systems. Concrete walls constructed
                                    8
                                                              in  accordance  with  these  provisions  shall  comply  with  the
                                                              shapes and minimum concrete cross-sectional dimensions of
                          SECTION R608                        Table R608.3.
           EXTERIOR CONCRETE WALL CONSTRUCTION                   R608.3.1  Flat  wall  systems.  Flat concrete wall systems
         R608.1 General. Exterior concrete walls shall be designed and  shall comply with Table R608.3 and Figure R608.3(1) and
         constructed in accordance with the provisions of this section or  have a minimum nominal thickness of 4 inches (102 mm).
         in accordance with the provisions of PCA 100 or ACI 318.
         Where PCA 100, ACI 318 or the provisions of this section are  R608.3.2  Waffle-grid  wall  systems.  Waffle-grid  wall
         used to design concrete walls, project drawings, typical details  systems  shall  comply  with  Table  R608.3  and  Figure
         and specifications are not required to bear the seal of the archi-  R608.3(2) and shall have a minimum nominal thickness of
         tect  or  engineer  responsible  for  design,  unless  otherwise  6 inches (152 mm) for the horizontal and vertical concrete
         required by the state law of the jurisdiction having authority.  members (cores). The core and web dimensions shall com-
                                                                 ply with Table R608. 3. The maximum weight of waffle-
                                                                 grid walls shall comply with Table R608.3.