Page 300 - 2018_IRC
P. 300

WALL CONSTRUCTION



               R607.3.2 Thin units. The specified thickness of thin units  R607.4.4 Curved panels. The width of curved panels shall
                                  1
               shall be not less than 3 /  inches (79 mm) for hollow units  conform  to  the  requirements  of  Sections  R607.4.1,
                                   8
               and not less than 3 inches (76 mm) for solid units.   R607.4.2 and R607.4.3, except additional structural sup-
             R607.4  Isolated  panels.  Isolated  panels  of  glass  unit  ports shall be provided at locations where a curved section
             masonry shall conform to the requirements of this section.  joins a straight section, and at inflection points in multiple-
                                                                     curve walls.
               R607.4.1 Exterior standard-unit panels. The maximum
               area  of  each  individual standard-unit  panel  shall  be  144  R607.5 Panel support. Glass unit masonry panels shall con-
                               2
               square feet (13.4 m ) where the design wind pressure is 20  form to the support requirements of this section.
               pounds per square foot (958 Pa). The maximum area of  R607.5.1  Deflection.  The  maximum  total  deflection  of
               such panels subjected to design wind pressures other than  structural members that support glass unit masonry shall
                                                                              l
               20 pounds per square foot (958 Pa) shall be in accordance  not exceed / .
                                                                              600
               with  Figure  R607.4.1.  The  maximum  panel  dimension  R607.5.2  Lateral  support.  Glass  unit  masonry  panels
               between structural supports shall be 25 feet (7620 mm) in  shall be laterally supported along the top and sides of the
               width or 20 feet (6096 mm) in height.                 panel. Lateral supports for glass unit masonry panels shall
               R607.4.2 Exterior thin-unit panels. The maximum area  be designed to resist not less than 200 pounds per lineal
               of each individual thin-unit panel shall be 85 square feet  feet  (2918  N/m)  of  panel,  or  the  actual  applied  loads,
                     2
               (7.9  m ).  The  maximum  dimension  between  structural  whichever is greater. Except for single-unit panels, lateral
               supports shall be 15 feet (4572 mm) in width or 10 feet  support shall be provided by panel anchors along the top
               (3048 mm) in height. Thin units shall not be used in appli-  and sides spaced not greater than 16 inches (406 mm) on
               cations where the design wind pressure as stated in Table  center  or  by  channel-type  restraints.  Single-unit  panels
               R301.2(2) exceeds 20 pounds per square foot (958 Pa).  shall be supported by channel-type restraints.
               R607.4.3  Interior  panels.  The  maximum  area  of  each  Exceptions:
               individual  standard-unit  panel  shall  be  250  square  feet  1. Lateral support is not required at the top of panels
                      2
               (23.2 m ). The maximum area of each thin-unit panel shall    that are one unit wide.
               be  150  square  feet  (13.9  m ).  The  maximum  dimension
                                      2
               between structural supports shall be 25 feet (7620 mm) in  2. Lateral support is not required at the sides of pan-
               width or 20 feet (6096 mm) in height.                        els that are one unit high.
                              70


                              60



                              50
                             DESIGN WIND PRESSURE (psf)  40  STANDARD UNIT





                                                             PANELS
                              30


                              20



                              10


                               0
                                0          50         100        150        200         250        300
                                                  MAXIMUM AREA OF PANEL (SQUARE FEET)


              For SI: 1 square foot = 0.0929 m , 1 pound per square foot = 0.0479 kPa.
                                   2
                                                          FIGURE R607.4.1
                                          GLASS UNIT MASONRY DESIGN WIND LOAD RESISTANCE