WALL CONSTRUCTION



                ends of walls, and at a maximum spacing of 10 feet   anchored  around  vertical  reinforcing  bars  with  a
                (3048 mm).                                           standard hook.
                   Horizontal  joint  reinforcement  shall  consist  of  R606.12.3.3  Minimum  reinforcement  for  masonry
                not  less  than  two  wires  of  W1.7  spaced  not  more  columns.  Lateral  ties  in  masonry  columns  shall  be
                than 16 inches (406 mm); or bond beam reinforce-   spaced not more than 8 inches (203 mm) on center and
                                                                                     3
                ment of not less than one No. 4 bar spaced not more  shall be not less than  / -inch (9.5 mm) diameter. Lat-
                                                                                      8
                than 10 feet (3048 mm) shall be provided. Horizon-  eral ties shall be embedded in grout.
                tal  reinforcement  shall  be  provided  at  the  bottom  R606.12.3.4 Material restrictions. Type N mortar or
                and top of wall openings and shall extend not less  masonry cement shall not be used as part of the lateral
                than 24 inches (610 mm) nor less than 40 bar diame-  force-resisting system.
                ters  past  the  opening;  continuously  at  structurally
                connected  roof  and  floor  levels;  and  within  16  R606.12.3.5 Lateral tie anchorage. Standard hooks for
                inches (406 mm) of the top of walls.               lateral tie anchorage shall be either a 135-degree (2.4 rad)
           R606.12.3 Seismic Design Category D  or D . Structures  standard hook or a 180-degree (3.2 rad) standard hook.
                                                1
                                           0
           in Seismic Design Category D  or D  shall comply with  R606.12.4  Seismic  Design  Category  D .  Structures  in
                                                                                                   2
                                     0
                                          1
           the requirements of Seismic Design Category C and the  Seismic  Design  Category  D   shall  comply  with  the
                                                                                          2
           additional  requirements  of  this  section.  AAC  masonry  requirements  of  Seismic  Design Category D  and  to the
                                                                                                      1
           shall not be used for the design of masonry elements that  additional requirements of this section.
           are part of the lateral force-resisting system.         R606.12.4.1 Design of elements not part of the lateral
              R606.12.3.1 Design requirements. Masonry elements    force-resisting system. Stack bond masonry that is not
              other than those covered by Section R606.12.2.2.2 shall  part of the lateral force-resisting system shall have a hor-
              be  designed  in  accordance  with  the  requirements  of  izontal cross-sectional area of reinforcement of not less
              Chapters 1 through 7 and Sections 8.1 and 8.3 of TMS  than  0.0015  times  the  gross  cross-sectional  area  of
              402,  ACI  530/ASCE  5  and  shall  meet  the  minimum  masonry. Table R606.12.4.1 shows minimum reinforc-
              reinforcement  requirements  contained  in  Sections  ing bar sizes for masonry walls. The maximum spacing
              R606.12.3.2  and  R606.12.3.2.1.  Otherwise,  masonry  of horizontal reinforcement shall be 24 inches (610 mm).
              shall be designed in accordance with TMS 403.        These elements shall be solidly grouted and shall be con-
                                                                   structed of hollow open-end units or two wythes of solid
                Exception:  Masonry  walls  limited  to  one  story  in  units.
                height  and  9  feet  (2743  mm)  between  lateral  sup-
                                                                                TABLE R606.12.4.1
                ports  need  not  be  designed  provided  they  comply  MINIMUM REINFORCING FOR STACKED BONDED
                with  the  minimum  reinforcement  requirements  of  MASONRY WALLS IN SEISMIC DESIGN CATEGORY D 2
                Sections R606.12.3.2 and R606.12.3.2.1.          NOMINAL WALL THICKNESS     MINIMUM BAR SIZE
              R606.12.3.2 Minimum reinforcement requirements            (inches)           SPACED AT 24 INCHES
              for  masonry  walls.  Masonry  walls  other  than  those    6                       #4
              covered by Section R606.12.2.2.3 shall be reinforced in     8                       #5
              both the vertical and horizontal direction. The sum of      10                      #5
              the cross-sectional area of horizontal and vertical rein-   12                      #6
              forcement shall be not less than 0.002 times the gross  For SI: 1 inch = 25.4 mm.
              cross-sectional  area  of  the  wall,  and  the  minimum  R606.12.4.2  Design  of  elements  part  of  the  lateral
              cross-sectional area in each direction shall be not less  force-resisting system. Stack bond masonry that is part
              than 0.0007 times the gross cross-sectional area of the  of the lateral force-resisting system shall have a horizon-
              wall.  Reinforcement  shall  be  uniformly  distributed.  tal cross-sectional area of reinforcement of not less than
              Table R606.12.3.2 shows the minimum reinforcing bar  0.0025 times the gross cross-sectional area of masonry.
              sizes  required  for  varying  thicknesses  of  masonry  Table R606.12.4.2 shows minimum reinforcing bar sizes
              walls. The maximum spacing of reinforcement shall be  for masonry walls. The maximum spacing of horizontal
              48 inches (1219 mm) provided that the walls are solid  reinforcement shall be 16 inches (406 mm). These ele-
              grouted and constructed of hollow open-end units, hol-  ments shall be solidly grouted and shall be constructed of
              low  units laid with full head  joints or  two wythes of  hollow open-end units or two wythes of solid units.
              solid  units.  The  maximum  spacing  of  reinforcement
                                                                                TABLE R606.12.4.2
              shall be 24 inches (610 mm) for all other masonry.    MINIMUM REINFORCING FOR STACKED BONDED
                R606.12.3.2.1 Shear wall reinforcement require-   MASONRY WALLS IN SEISMIC DESIGN CATEGORY D 2
                ments. The maximum spacing of vertical and hori-  NOMINAL WALL THICKNESS     MINIMUM BAR SIZE
                zontal  reinforcement  shall  be  the  smaller  of  one-  (inches)         SPACED AT 16 INCHES
                third  the  length  of  the  shear  wall,  one-third  the  6                      #4
                height of the shear wall, or 48 inches (1219 mm).         8                       #5
                The minimum cross-sectional area of vertical rein-        10                      #5
                                                                          12
                                                                                                  #6
                forcement  shall  be  one-third  of  the  required  shear
                reinforcement.  Shear  reinforcement  shall  be  For SI: 1 inch = 25.4 mm.

             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               273