Page 299 - 2018_IRC
P. 299

WALL CONSTRUCTION


                                                                                                        2
         R606.13 Multiple-wythe masonry. The facing and backing    than one tie for each 2.67 square feet (0.248 m ) of wall
         of multiple-wythe masonry walls shall be bonded in accor-  area. Neither the vertical nor the horizontal spacing of
         dance with Section  R606.13.1,  R606.13.2  or R606.13.3.  In  the adjustable wall ties shall exceed 24 inches (610 mm).
         cavity walls, neither the facing nor the backing shall be less  The  maximum  vertical  offset  of  bed  joints  from  one
         than 3 inches (76 mm) nominal in thickness and the cavity  wythe to the other shall be 1.25 inches (32 mm). The
         shall be not more than 4 inches (102 mm) nominal in width.  maximum clearance between connecting parts of the ties
                                                                         1
         The backing shall not be less than the thickness of the facing.  shall be  /  inch (2 mm). Where pintle legs are used, ties
                                                                           16
                                                                                           3
           Exception:  Cavities  shall  be  permitted  to exceed the  4-  shall have not less than two  / -inch-diameter (5 mm)
                                                                                            16
           inch (102 mm) nominal dimension provided that tie size  legs.
           and tie spacing have been established by calculation.   R606.13.2.3 Bonding with prefabricated joint rein-
           R606.13.1  Bonding  with  masonry  headers.  Bonding    forcement.  Where  the  facing  and  backing  (adjacent
           with solid or hollow masonry headers shall comply with  wythes) of masonry are bonded with prefabricated joint
           Sections R606.13.1.1 and R606.13.1.2.                   reinforcement,  there  shall  be  not  less  than  one  cross
                                                                   wire serving as a tie for each 2.67 square feet (0.248
              R606.13.1.1 Solid units. Where the facing and backing  m ) of wall area. The vertical spacing of the joint rein-
                                                                     2
              (adjacent  wythes)  of  solid masonry  construction  are  forcement shall not exceed 16 inches (406 mm). Cross
              bonded by means of masonry headers, not less than 4  wires on prefabricated joint reinforcement shall not be
              percent of the wall surface of each face shall be com-  smaller than No. 9 gage. The longitudinal wires shall be
              posed of headers extending not less than 3 inches (76  embedded in the mortar.
              mm) into the backing. The distance between adjacent
              full-length  headers  shall  not  exceed  24  inches  (610  R606.13.3 Bonding with natural or cast stone. Bonding
              mm) either vertically or horizontally. In walls in which  with  natural  and  cast  stone  shall  conform  to  Sections
              a single header does not extend through the wall, head-  R606.13.3.1 and R606.13.3.2.
              ers from the opposite sides shall overlap not less than 3  R606.13.3.1  Ashlar  masonry.  In  ashlar  masonry,
              inches (76 mm), or headers from opposite sides shall be  bonder units, uniformly distributed, shall be provided
              covered  with  another  header  course  overlapping  the  to the extent of not less than 10 percent of the wall area.
              header below not less than 3 inches (76 mm).         Such bonder units shall extend not less than 4 inches
                                                                   (102 mm) into the backing wall.
              R606.13.1.2 Hollow units. Where two or more hollow
              units are used to make up the thickness of a wall, the  R606.13.3.2  Rubble  stone  masonry.  Rubble  stone
              stretcher courses shall be bonded at vertical intervals not  masonry 24 inches (610 mm) or less in thickness shall
              exceeding 34 inches (864 mm) by lapping not less than 3  have bonder units with a maximum spacing of 3 feet
              inches (76 mm) over the unit below, or by lapping at ver-  (914 mm) vertically and 3 feet (914 mm) horizontally,
              tical intervals not exceeding 17 inches (432 mm) with  and  if  the  masonry  is  of  greater  thickness  than  24
              units that are not less than 50 percent thicker than the  inches (610 mm), shall have one bonder unit for each 6
                                                                                   2
              units below.                                         square feet (0.557 m ) of wall surface on both sides.
           R606.13.2  Bonding  with  wall  ties  or  joint  reinforce-  R606.14 Anchored and adhered masonry veneer.
           ment. Bonding with wall ties or joint reinforcement shall  R606.14.1 Anchored veneer. Anchored masonry veneer
           comply with Section R606.13.2.3.                      installed over a backing of wood or cold-formed steel shall
              R606.13.2.1 Bonding with wall ties. Bonding with wall  meet the requirements of Section R703.8.
              ties, except as required by Section R607, where the fac-  R606.14.2  Adhered  veneer.  Adhered  masonry  veneer
              ing and backing (adjacent wythes) of masonry walls are  shall be installed in accordance with the requirements of
                        3
              bonded with  / -inch-diameter (5 mm) wall ties embed-  Section R703.12.
                         16
              ded in the horizontal mortar joints, there shall be not less
                                    1
                                                       2
              than one metal tie for each 4 /  square feet (0.418 m ) of
                                     2
              wall area. Ties in alternate courses shall be staggered.          SECTION R607
              The maximum vertical distance between ties shall not         GLASS UNIT MASONRY
              exceed 24 inches (610 mm), and the maximum horizon-  R607.1  General.  Panels  of  glass  unit  masonry  located  in
              tal distance shall not exceed 36 inches (914 mm). Rods  load-bearing and nonload-bearing exterior and interior walls
              or ties bent to rectangular shape shall be used with hol-  shall be constructed in accordance with this section.
              low masonry units laid with the cells vertical. In other
              walls, the ends of ties shall be bent to 90-degree (0.79  R607.2 Materials. Hollow glass units shall be partially evac-
                                                                                                             3
              rad) angles to provide hooks not less than 2 inches (51  uated and have a minimum average glass face thickness of  / 16
              mm) long. Additional bonding ties shall be provided at  inch (5 mm). The surface of units in contact with mortar shall
              all openings, spaced not more than 3 feet (914 mm) apart  be  treated  with  a  polyvinyl  butyral  coating  or  latex-based
              around the perimeter and within 12 inches (305 mm) of  paint. The use of reclaimed units is prohibited.
              the opening.                                    R607.3 Units. Hollow or solid glass block units shall be stan-
              R606.13.2.2 Bonding with adjustable wall ties. Where  dard or thin units.
              the facing and backing (adjacent wythes) of masonry are  R607.3.1 Standard units. The specified thickness of stan-
              bonded with adjustable wall ties, there shall be not less  dard units shall be not less than 3 /  inches (98 mm).
                                                                                           7
                                                                                            8