Page 87 - 2018_IRC
P. 87

BUILDING PLANNING



           R302.10.2  Loose-fill  insulation.  Loose-fill  insulation  2. Two thicknesses of 1-inch (25.4 mm) nominal lum-
           materials that cannot be mounted in the ASTM E84 or UL    ber with broken lap joints.
           723 apparatus without a screen or artificial supports shall  3. One thickness of  / -inch (18.3 mm) wood struc-
                                                                                    23
                                                                                      32
           comply with the flame spread and smoke-developed limits   tural  panels  with  joints  backed  by  / -inch  (18.3
                                                                                                   23
           of  Section  R302.10.1  where  tested  in  accordance  with  mm) wood structural panels.  32
           CAN/ULC S102.2.
                                                                                    3
                                                                   4. One  thickness  of  / -inch  (19.1  mm)  particleboard
                                                                                      4
              Exception:  Cellulosic  fiber  loose-fill  insulation  shall  with  joints  backed  by  / -inch  (19.1  mm)  particle-
                                                                                        3
              not be required to be tested in accordance with CAN/   board.               4
              ULC  S102.2,  provided  that  such  insulation  complies
              with  the  requirements  of  Sections  R302.10.1  and  5. One-half-inch (12.7 mm) gypsum board.
              R302.10.3.                                           6. One-quarter-inch (6.4 mm) cement-based millboard.
           R302.10.3  Cellulosic  fiber  loose-fill  insulation.  Cellu-  7. Batts or blankets of mineral wool or glass fiber or
           losic fiber loose-fill insulation shall comply with CPSC 16  other approved materials installed in such a manner
           CFR, Parts 1209 and 1404. Each package of such insulat-   as to be securely retained in place.
           ing  material  shall  be  clearly  labeled  in  accordance  with
           CPSC 16 CFR, Parts 1209 and 1404.                       8. Cellulose insulation installed as tested in accordance
                                                                     with ASTM E119 or UL 263, for the specific appli-
           R302.10.4 Exposed attic insulation. Exposed insulation    cation.
           materials installed on attic floors shall have a critical radi-
           ant flux of not less than 0.12 watt per square centimeter.  R302.11.1.1  Batts  or  blankets  of  mineral  or  glass
                                                                   fiber.  Batts  or  blankets  of  mineral  or  glass  fiber  or
           R302.10.5 Testing. Tests for critical radiant flux shall be  other  approved  nonrigid  materials  shall  be  permitted
           made in accordance with ASTM E970.                      for compliance with the 10-foot (3048 mm) horizontal
         R302.11  Fireblocking.  In  combustible  construction,  fire-  fireblocking in walls constructed using parallel rows of
         blocking shall be provided to cut off both vertical and hori-  studs or staggered studs.
         zontal concealed draft openings and to form an effective fire  R302.11.1.2  Unfaced  fiberglass.  Unfaced  fiberglass
         barrier between stories, and between a top story and the roof  batt insulation used as fireblocking shall fill the entire
         space.                                                    cross section of the wall cavity to a height of not less
           Fireblocking shall be provided in wood-framed construc-  than 16 inches (406 mm) measured vertically. Where
         tion in the following locations:                          piping, conduit or similar obstructions are encountered,
                                                                   the  insulation  shall  be  packed  tightly  around  the
           1. In concealed spaces of stud walls and partitions, includ-  obstruction.
              ing  furred  spaces  and  parallel  rows  of  studs  or  stag-
              gered studs, as follows:                             R302.11.1.3 Loose-fill insulation material. Loose-fill
                                                                   insulation  material  shall  not  be  used  as  a  fireblock
                1.1. Vertically at the ceiling and floor levels.
                                                                   unless  specifically  tested  in  the  form  and  manner
                1.2. Horizontally at intervals not exceeding 10 feet  intended for use to demonstrate its ability to remain in
                    (3048 mm).                                     place and to retard the spread of fire and hot gases.
           2. At  interconnections  between  concealed  vertical  and  R302.11.2 Fireblocking integrity. The integrity of fire-
              horizontal spaces such as occur at soffits, drop ceilings  blocks shall be maintained.
              and cove ceilings.                              R302.12 Draftstopping. In combustible construction where
           3. In concealed spaces between stair stringers at the top  there  is  usable  space  both  above  and  below  the  concealed
              and  bottom  of  the  run.  Enclosed  spaces  under  stairs  space of a floor-ceiling assembly, draftstops shall be installed
              shall comply with Section R302.7.               so that the area of the concealed space does not exceed 1,000
                                                                               2
           4. At  openings  around  vents,  pipes,  ducts,  cables  and  square  feet  (92.9  m ).  Draftstopping  shall  divide  the  con-
              wires at ceiling and floor level, with an approved mate-  cealed  space  into  approximately  equal  areas.  Where  the
              rial to resist the free passage of flame and products of  assembly is enclosed by a floor membrane above and a ceil-
              combustion.  The  material  filling  this  annular  space  ing  membrane  below,  draftstopping  shall  be  provided  in
              shall not be required to meet the ASTM E136 require-  floor-ceiling assemblies under the following circumstances:
              ments.                                             1. Ceiling is suspended under the floor framing.
           5. For  the  fireblocking  of  chimneys  and  fireplaces,  see  2. Floor framing is constructed of truss-type open-web or
              Section R1003.19.                                    perforated members.
           6. Fireblocking  of  cornices  of  a  two-family  dwelling  is  R302.12.1 Materials. Draftstopping materials shall be not
                                                                         1
                                                                                                      3
              required at the line of dwelling unit separation.  less than  / -inch (12.7 mm) gypsum board,  / -inch (9.5
                                                                          2
                                                                                                       8
           R302.11.1 Fireblocking materials. Except as provided in  mm) wood structural panels or other approved materials
           Section R302.11, Item 4, fireblocking shall consist of the  adequately supported. Draftstopping shall be installed par-
           following materials.                                  allel  to  the  floor  framing  members  unless  otherwise
                                                                 approved  by  the  building official.  The  integrity  of  the
              1. Two-inch (51 mm) nominal lumber.                draftstops shall be maintained.

         62                                                                  2018 INTERNATIONAL RESIDENTIAL CODE  ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   82   83   84   85   86   87   88   89   90   91   92