                        Within this amended mandate,         of heater input [clause 7.37.2(c)].
                        new deadlines were announced
                        for TSSA calculations to be com-     Maximum input of the heating
                        pleted for facilities with heaters   appliances does not exceed 20
                        installed prior to October 1, 2014,  BTUH/FT3 of the space in which
                        as follows:                          the appliance is located [clause
                                                             7.37.2(d)].
                        a. by July 1, 2019, when total
                           building area housing             Once these calculations have
                           livestock or poultry on the       been completed, Stonecrest
                           premise is over 25,000 square     Engineering requires a site visit to
                           feet;                             verify the equipment in support
                                                             of the required calculations.
                        b. by July 1, 2021 when total        This is to confirm that the
                           building area housing             minimum ventilation rate of
                           livestock or poultry on the       the barn (mechanical or natural
                           premise is up to and including    ventilation) when the heaters
                           25,000 square feet.               are operating is not less than 300
                                                             CFM / 100,000 BTUH (0.003 CFM/
                        The calculations required for        BTUH) of heaters input; and to
                        your heaters must be verified by     ensure the maximum input of
                        a licensed professional engineer,    the heating appliances does not
                        licensed engineering technologist    exceed 20 BTUH/FT3 of the space
                        or other limited license holder,     in which the appliance is located.
                        pursuant to the Professional
                        Engineers Act. The PEO license       Ensuring compliance with the
                        holder must verify the following     TSSA mandate now will ensure
                        two (2) calculations:                you continue to receive uninter-
                                                             rupted delivery of fuel. For more
                          Minimum ventilation rate of        information, please contact the
                        the barn (mechanical or natural      TSSA Fuels Safety Program Tech-
                        ventilation) when the heaters are    nical Services at 1-877-682-8772
                        operating is not less than 300 CFM   or email fuels_technical_servic-
                        / 100,000 BTUH (0.003 CFM/BTUH)      es@tssa.org.