Page 102 - Vessel Sanitation Program 2018 Construction Guidelines
P. 102

VSP 2018 Construction Guidelines



                                entrapment issues; cover/grate secondary layer of protection; related sump
                                design; and features specific to the RECREATIONAL WATER FACILITY.


                       28.1.5   Alternate to Marking Field Fabricated Fittings
                                As an alternate to marking custom/shipyard constructed (field fabricated)  drain
                                cover fittings, the owner of the facility where these fittings will be  installed
                                must be advised in writing by the registered design professional of  the
                                information set forth in section 7.1.1 of ASME A112.19.8-2007.

                       28.1.6   Accompanying Letter
                                A letter from the shipyard must accompany each custom/shipyard constructed
                                (field fabricated) drain cover fitting. At a minimum, the letter must specify the
                                shipyard, name of the vessel, specifications and dimensions of the drain cover,
                                as noted above, and the exact location of the RECREATIONAL WATER
                                FACILITY for which it was designed.  The registered design professional’s
                                name, contact information, and signature  must be on the letter.

                       28.1.7   Antientrapment/Antientanglement Requirements
                                See Table 28.1.7 for ANTIENTRAPMENT and ANTIENTANGLEMENT
                                requirements for drains and SUCTION FITTINGS in RECREATIONAL
                                WATER FACILITIES.

                       Table 28.1.7 ANTIENTRAPMENT Requirements for RECREATIONAL WATER
                       FACILITIES
                       (Does not include facilities designed with zero depth and drains not under direct suction)
                                                                                                 Secondary
                                                                                                 ANTI-
                  Option*  Type         Drainage/Recirculation System    Cover Design            ENTRAPMENT
                  1        GRAVITY  Multiple drains (2 or more drains    Standard design (not    Alarm
                           only         greater than 1 meter [3 feet] apart)   compliant  with ASME
                                                                         A112.19.8)
                  2        GRAVITY  Multiple drains (2 or more drains    ASME A112.19.8          None
                           only         greater than 1 meter [3 feet] apart)   compliant cover

                  3        GRAVITY  Single UNBLOCKABLE DRAIN             Standard design (not    Alarm
                           only         (per ASME A112.19.8)             compliant with ASME

                  4        GRAVITY  Single UNBLOCKABLE DRAIN             ASME A112.19.8          None
                           only         (per ASME A112.19.8)             compliant cover
                  5        GRAVITY  Single BLOCKABLE DRAIN or            ASME A112.19.8          GDS
                           only         multiple drains (less than 1 meter   compliant cover
                                        [3 feet] apart)
                  6        SUCTION      Multiple drains (2 or more drains   ASME A112.19.8       None
                           FITTING      per pump with drains greater than   compliant cover
                                        1 meter [3 feet] apart)
                  7        SUCTION      Single UNBLOCKABLE DRAIN         ASME A112.19.8          SVRS or APS
                           FITTING      (per ASME A112.19.8-2007)        compliant cover