VSP 2018 Construction Guidelines



                                        Point sample cocks down and identify them with the appropriate tank
                                        number.


                       22.7.2   Storage Tank Access Hatch

                          22.7.2.1      Installation
                                        Install an access hatch for entry on the sides of POTABLE WATER
                                        TANKS.


                       22.7.3   Storage Tank Water Level

                          22.7.3.1      Automatic
                                        Provide an automatic method for determining the water level of
                                        POTABLE WATER TANKS. Visual sight glasses are acceptable.


                       22.7.4   Storage Tank Vents

                          22.7.4.1      Location
                                        Ensure that air-relief vents end at least 1,000 millimeters (40 inches)
                                        above the maximum load level of the vessel.

                                        Make the cross-sectional area of vents equal to or greater than that of
                                        the tank filling line.

                                        Position the end of the vents so openings face down or are otherwise
                                        protected, and install a 16-mesh corrosion-resistant screen.

                          22.7.4.2      Single Pipe
                                        A single pipe may be used as a combination vent and overflow.

                          22.7.4.3      Vent Connections
                                        Do not connect the vent of a POTABLE WATER TANK to the vent of
                                        a  tank that is not a POTABLE WATER TANK.

                       22.7.5   Storage Tank Drains

                          22.7.5.1      Design
                                        Design tanks to drain completely.

                          22.7.5.2      Drain Opening
                                        Provide a drain opening at least 100 millimeters (4 inches) in  diameter
                                        that preferably matches the diameter of the inlet pipe.

                          22.7.5.3      Suction Pump
                                        If drained by a suction pump, provide a sump and install the pump
                                        suction port in the bottom of the sump.