Page 91 - Vessel Sanitation Program 2018 Construction Guidelines
P. 91

VSP 2018 Construction Guidelines



                                This does not include the following:
                                   •  Discharges from DECK DRAINS on open decks.
                                   •  Cooling lines with no chemical treatment.
                                   •  Alarmed vent/overflow pipes for GRAY WATER, treated GRAY or
                                       BLACK WATER, and ballast tank with an automatic shutoff system for
                                       SANITARY SEAWATER intake. These alarms must be visual and
                                       audible and must sound in a space that is continuously occupied.
                                   •  Alarmed emergency bilge discharge lines with an automatic shutoff
                                       system for SANITARY SEAWATER intake. These alarms must be
                                       visual and audible and must sound in a space that is continuously
                                       occupied. GRAY and BLACK WATER cannot be able to be transferred
                                       to the bilge with this type of design.
                                   •  Alarmed emergency ballast discharge line with an automatic shutoff
                                       system for SANITARY SEAWATER intake. These alarms must be
                                       visual and audible and must sound in a space that is continuously
                                       occupied.
                                   •  Discharges from the anchor chain locker are allowed forward of the sea
                                       chest if the chain is rinsed/cleaned only with sea water.
                                   •  Alarmed vent/overflow pipes for heeling tanks and laundry water
                                       storage tanks with an automatic shutoff system for SANITARY
                                       SEAWATER intake are allowed. These alarms must be visual and
                                       audible and must sound in a space that is continuously occupied.

                       22.13.2  Direct Connections
                                Use only direct connections from the evaporators and reverse osmosis plants  to
                                the POTABLE WATER system.

                       22.13.3  Potable and Nonpotable Water Systems
                                If an evaporator or reverse osmosis plant makes water for both the POTABLE
                                WATER system and a nonpotable water system, install an AIR GAP or RP
                                ASSEMBLY on the line supplying the nonpotable water system.

                                Onboard water sources such as TECHNICAL WATER, air conditioning
                                condensate, or wastewater of any kind (treated or untreated) are not allowed for
                                POTABLE WATER production.


                       22.13.4  Instructions
                                Post narrative, step-by-step operating instructions for manually operated
                                evaporators and for any reverse osmosis plants near the units.

                       22.13.5  Discharge to Waste
                                Ensure water production units connected to the POTABLE WATER system
                                have the ability to discharge to waste if the distillate is not fit for use.








                                                             75