Page 93 - Vessel Sanitation Program 2018 Construction Guidelines
P. 93

VSP 2018 Construction Guidelines



                                        recommendation. Provide all manufacturers’ literature for installation,
                                        operation, and maintenance.


                          22.14.2.2     Free Halogen Probes
                                        Use probes to measure free HALOGEN and link them to the
                                        analyzer/controller and chemical dosing pumps.


                          22.14.2.3     Backup Halogenation Pump
                                        Provide a back-up HALOGENATION pump with an automatic
                                        switchover that begins pumping HALOGEN when the primary (in-use)
                                        pump fails or cannot meet the HALOGENATION demand.

                          22.14.2.4     Chemical Injection Dosing Point
                                        A check valve or nonreturn valve must be installed between the
                                        distribution halogen and pH pumps and the injection points. In
                                        addition,
                                           •  The potable water distribution halogenation and pH chemical
                                               injection dosing points must be located on the delivery line
                                               downstream of the potable water pumps, OR
                                           •  If the injection dosing point is before the potable water pumps,
                                               it must be located above the chemical dosing tanks.

                          22.14.2.5     Probe/Sample Location
                                        Locate the HALOGEN analyzer probe at a distant point in each
                                        distribution system loop where significant water flow exists.


                          22.14.2.6     Alarm
                                        Provide an audible alarm in a continually occupied watch station (e.g.,
                                        the engine control room or bridge) to indicate low or high free
                                        HALOGEN readings at each distant point analyzer.

                          22.14.2.7     Backflow Prevention
                                        Provide POTABLE WATER taps with appropriate BACKFLOW
                                        prevention at HALOGEN supply tanks.

                          22.14.2.8     Free Halogen Analyzer-Chart Recorder
                                        Provide continuous recording free HALOGEN analyzer-chart
                                        recorder(s) that have ranges of 0.0 to 5.0 MG/L (ppm) and indicate the
                                        level of free HALOGEN for 24-hour time periods (e.g., circular 24-
                                        hour charts).

                                        Electronic data loggers with CERTIFIED DATA SECURITY
                                        FEATURES may be installed in lieu of chart recorders. Acceptable
                                        data loggers produce records that conform to the principles of operation
                                        and data display required of the analog charts, including printing the
                                        records. Use electronic data loggers that log times in increments of




                                                             77