•  Activation - Provides a secure, software-based sys-
                                                                        detects alarm conditions and publishes event informa-
                    tem for activating Rockwell Software products.      downloaded into a Logix controller. The controller
                 •  Alarm and Events - Provides both server-based       tion, which is routed through the system for display
                    and device-based process control alarm server.      and logging.
                                                                        Tag-based - Software-based tag servers monitor data
                  FactoryTalk alarms and events support the following
               two types of alarm monitoring (Figure 14-50):            tags for alarm conditions and publish event information
                                                                        for display and logging. Tag-based alarm monitoring
                  Device-based - Pre-built alarm instructions that      is supported by Logix 5000 controllers and SLC 500
                  are programmed in a Logix 5000 project and then       controllers.






                  FactoryTalk Alarms and              Using FactoryTalk  FactoryTalk Alarms and              Using FactoryTalk
               Events services routes alarm 4  FactoryTalk  5  View SE Clients,  Events services routes alarm  3  FactoryTalk  4  View SE Clients,
                 information to logs and to  Alarms and Events  operators interact  information to logs and to  Alarms and Events  operators interact
                  Alarm and Event objects  services   with alarms (for   Alarm and Event objects  services   with alarms (for
                   embedded in graphic                example,         embedded in graphic                   example,
                displays in FactoryTalk View          acknowledge,  displays in FactoryTalk View             acknowledge,
                   Device server notifies  3           suppress) from                                         suppress) from
                  FactoryTalk Alarms and              graphic displays  Tag Alarm and Event Server  2        graphic displays
                  Events services of alarm                           polls controller to monitor
                       state changes       Alarm and Event            alarms and then notifies
                                           History log               users of alarm conditions   Alarm and Event
                                                                                                 History log
                                    2 Controller detects alarm
                                      conditions and notifies device
                                      server of changes in alarm states
                                                                                    1
                                1
                                                                       Logic in a controller is
                    RSLogix 5000 alarm                                 programmed to detect
               instructions are programmed                            problems and latch fault
                and then downloaded into                            conditions in controller tags
                       the controller                                       or addresses
                               (a) Device-based alarms                                (b) Tag-based alarms
               Figure 14-50  FactoryTalk alarm monitoring.
               Source: Images Courtesy of Rockwell Automation, Inc.








































               330        Chapter 14  Process Control, Network Systems, and SCADA