Page 65 - GuardII+ Series 4208 Platform PD User Manual
P. 65

User Instructions




                                     NOTE:
                                     If using a Remote I/O Unit, then the ASIM/DSIM configuration will be a
                                     more  collaborative  effort;  it  will  depend  on  the  exact  Remote  I/O  Unit
                                     assembly, which analog signals are connected to which inputs, and the
                                     translation from the analog signal to the actual Operating Condition being
                                     measured.

































                                        Figure 6-23 Operating Condition Configuration

              6.3.3.  Partial Discharge Input Configuration

                        The  first  part  of  the  PD  system  configuration  is  to  select  the  User  Range  sensitivity,
                     synchronization source and phase adjustment for each input.  This is also where the BUS
                     delay is entered for a BUS PD system.
                        The ‘Detect Sensitivity’ function will run a series of single-shot measurements to find the
                     appropriate User Range for the current PD levels.

                        Single-shot PD measurements can also be run from this screen using the displayed phase
                     and settings.

                                     NOTE:
                                     Each  input  can  be  individually  disabled  by  selecting  the  ‘Disabled’
                                     sensitivity.  When this is done, the User, Auto and Alert Ranges will all be
                                     turned off for that input.