User Instructions



































                                          Figure 6-24 Sample PD Input Configuration
              6.3.4.  Operating Condition Trigger Configuration

                        The second part of the PD system configuration is to set Operating Condition  Trigger
                     Thresholds; enter the Full Load and Reduced Load power thresholds, and then the Hot and
                     Cold asset temperature thresholds.  Press the ‘Load Defaults’ button to set these thresholds
                     according to the asset’s active power and asset temperature ratings.
                        The  User  Defined  Trigger  (refer  to  Section  4.6.10)  is  also  configured  on  this  screen.
                     Enable it and select a time interval and minimum Qm threshold if desired.
                                     NOTE:
                                     When selecting a time interval for the User Defined Trigger, be sure to
                                     take the number of sensors into account; it takes less than 20 minutes to
                                     run a full set of PD measurements when there are 3 inputs, but a little over
                                     an hour to run a full set when there are 12 inputs.  So, setting a 30-minute
                                     time interval when the monitor has 12 inputs running will not produce a
                                     stable User Defined Trigger result.