Page 75 - GuardII+ Series 4208 Platform PD User Manual
P. 75

User Instructions



              6.7.2.  Delete Archives

                        This utility will delete all the Archives that are currently saved on the GuardII+.  This does
                     not affect current state of the Triggers or measurements that have already been downloaded
                     and/or imported into IAM; it only deletes the measurement data that is stored in the monitor.

                                     WARNING:
                                     Once the Archive is deleted in the GuardII+, it cannot be restored; do not
                                     use this utility unless you are sure that you do not need the Archived data.


              6.7.3.  Clear Trigger History
                        This utility will reset the Trigger status for all monitoring technologies.  The GuardII+ will
                     begin taking measurements as if no Triggers have ever occurred before.  This does not affect
                     the Archived or downloaded measurements; it only resets the Triggers.

                                     WARNING:
                                     Once the Triggers are reset in the GuardII+, they cannot be restored back
                                     to the previous status; do not use this utility unless you are sure that you
                                     want to start the Triggers over again.

              6.7.4.  Reset Alert

                        This  utility  will  reset  the  Alert state  of the monitor.   Note  that this  will  not  change  the
                     conditions that caused the Alert; for example, if the PD levels are still higher than the Very
                     High PD threshold, then the Alert will quickly occur again.

              6.7.5.  Get Diagnostics
                        This utility will get the latest diagnostic information from the monitor.  The diagnostics will
                     be saved in a file in the ‘Feedback Report Folder’ selected in IAM options; the file will be
                     named based on the date, time and serial number of the GuardII+.
                        The diagnostics include top-level hardware and system information such as whether the
                     hardware has been properly detected or whether the system is configured properly.  For rapid
                     resolution of any Technical Support issue, this should be included on any Technical Support
                     inquiry.
                        Any diagnostic failure will cause the Error indicator on the front panel to be activated.

              6.8.  Firmware Upgrades

                        Periodically, it may be necessary to update the firmware in the GuardII+.  This is done
                     using a USB drive like the data download procedure.  In this case, Iris Power LP will provide
                     a set of files that need to be loaded onto a USB drive that is then inserted into the monitor;
                     GuardII+ will upload the new firmware and then restart.










                                                              67
                                                                                          www.irispower.com