Page 92 - GuardII+ Series 4208 Platform PD User Manual
P. 92

Troubleshooting




                                     NOTE:
                                     If  PD  levels  do  suddenly  change  (either  a  pronounced  increase  or  a
                                     pronounced  decrease),  this  could  indicate  larger  issues  either  with  the
                                     asset being monitored or with the electrical system the asset is connected
                                     to.    It  is  highly  recommended  to  consult  with  Iris  Power  LP  Technical
                                     Support.


              7.4.2.  Swapping Inputs
                        If  measurements  from  one  input  are  showing  normal  measurement  results,  but
                     measurements from another input are not, temporarily swapping the input cables may help
                     determine if the problem is in the monitor or the not.

                        For  example,  if  measurements  from  Phase  A  show  a  normal  data  pattern,  but
                     measurements from Phase B do not, connect the Phase A cable to the Phase B input, and
                     the Phase B cable to the Phase A input; then use IAM to run single-shot measurements on
                     both inputs.

                        •  If the input that didn’t work properly still doesn’t, this indicates a problem with the Data
                            Acquisition Module; contact Iris Power LP Technical Support for assistance.

                        •  If the input that used to work no longer does, and the one that didn’t work now does,
                            this indicates a problem outside the monitor; in the cabling or the Termination.  Contact
                            Iris Power LP Technical Support for assistance.

              7.4.3.  3D Data

                        A  measurements’  3D  data  is  a  good  tool  to  interpret  what  is  happening;  however,
                     sometimes 3D data patterns are not obvious.  Contact Iris Power LP Technical Support for
                     assistance with data interpretation.

              7.4.4.  Alternate Monitor
                        If a second Iris Power LP instrument is available such as a portable instrument or a second
                     GuardII+,  this  can  be  used  for  validating  that  the  sensors  are  working  properly.    Run  a
                     measurement using the alternate instrument and compare the results to the GuardII+.
                        •  If the results are similar, then both instruments are likely working properly.
                        •  If the results are significantly different, then there is likely a problem with one of the
                            instruments.