                                    Figure 8-3 GuardII+ Hardware Overview – SSC PD Card

              8.2.  Modbus Register Map

                        GuardII+ hosts Modbus data registers that can be used by external devices to access the
                     PD results of the most recent set of measurements directly from a plant control system on the
                     same network.  This section describes the data registers hosted by the monitor.

                                     NOTE:
                                     The  GuardII+  Modbus  register  map  is  designed  for  compatibility  with
                                     Modbus Application Protocol Specification v1.1b3.


              8.2.1.  General Modbus Register Information
                        •  Each register is an F03 Holding Register

                        •  Unless otherwise noted, all data is expressed as 16-bit unsigned values
                        •  For values that are expressed as float data type, they are encoded as CD AB (or word-
                            swapped) floats.
                        •  To access the data registers, connect to the GuardII+’s Ethernet address and read the
                            desired register using the Modus over TCP/IP protocol