Page 100 - GuardII+ Series 4208 Platform PD User Manual
P. 100
Appendix
Address Range Data
48200 to 48263 Phase A Pair 1 2D Data
48500 to 48563 Phase B Pair 2 2D Data
48800 to 48863 Phase C Pair 3 2D Data
8.2.4. Bus PD Card Measurement Details
Address Data Notes
12000 User Range Phase A Pair 1 The year of the last measurement
Year Expressed in 4 digits (i.e., 2019)
12001 User Range Phase A Pair 1 The month of the last measurement
Month 1 = January … 12 = December
12002 User Range Phase A Pair 1 The day of the month of the last measurement
Day
12003 User Range Phase A Pair 1 The hour of the last measurement
Hour Expressed in 24-hour mode (0-23)
12004 User Range Phase A Pair 1 The minute of the last measurement
Minute 0-59
12005 User Range Phase A Pair 1 The second of the last measurement
Second 0-59
12006 Measurement Type This indicates the measurement range where:
0 = User Range
1 = Auto Range
2 = Alert Range
12007 User Range Phase A Pair 1 The number of AC cycles in the last
AC Cycles measurement
12008 User Range Phase A Pair 1 The AC Max Value – for Iris Power use only
AC Max Value
12009 User Range Phase A Pair 1 The AC Tick Count – for Iris Power use only
AC Tick Count
12010 User Range Phase A Pair 1 The measurement sensitivity
Sensitivity 0 = OFF or disabled
1 = 2mV-34mV
2 = 5mV-85mV
3 = 10mV-170mV
4 = 20mV-340mV
5 = 50mV-850mV
6 = 100mV-1700mV
7 = 200mV-3400mV
8 = 500mV-8500mV
9 = 1000mV-17000mV
10 = 2000mV-34000mV
12011 User Range Phase A Pair 1 AC Sync phase angle adjustment.
Phase Shift Expressed in degrees
92
www.irispower.com