RECESSED GYP MOUNTING INSTALLATION GUIDE (G/RG)


 1  2



 BLOCKING                                               C



 GYPSUM
 A




             A
 1




                                                    B



 B                              A
 3                                                4
 D/G JOINER



 C


                                                                               A

 ACL1/4 JOINER




                                                                               B
              B
 MUD  D
                ACL2/3/5 JOINER   C
 INSTALLATION STEPS

 Attention: Risk of fire and electrical shock - fixture to be installed by qualified electrician according to local codes and ordinances.
 Attention: Ensure proper handling of LEDs to limit common problems including: broken connection, loose wiring, and damage from electrostatic discharge.
 Attention: Aperature size must be maintained. Do not stretch fixture width to fasten to blocking.
 1  [A] - Wood or steel studs can be used for blocking, install gyp board then cut opening. For nominal   2  ROWS
         lengths reference dimensions in chart below, or consult submittal drawings for special lenght cut-outs.
               [A] - When rows are ordered, row sections will be labeled in sequence. Position section in proper
 [B]  - Power feed connections through KO hole: White+, Black-, Green, (if dimming is required): Purple Dim+,           order prior to installation (ie place 1 to 1).
         Grey Dim-  [B]  - Remove the lens. Apply suction cup (provided) to one end and carefully pull lens out.
 [C]  - Attach fixture to blocking through gyp with #8 drywall screws in the pre-drilled holes in the side   [C] - Remove reflectors (if applicable) and internal gear tray by unfastening hardware.
          flanges. Fixture must be fastened to blocking at a minimum of every 8” or less.
 [D] - Mud over side and end flanges to edge of fixture. Finish should just cover bottom extrusion edge.  3  [A] - Housing connection: White+, Black-, Green (if dimming is required): Purple Dim+, Grey Dim-
 NOMINAL ROUGH OPENING DIMENSIONS:  [B]  - Align corner pins and connect fixture housings with rubber mallet until no gap remains.
               [C] - Secure sections with joiner screws.
 NOMINAL LENGTH  12FT  10FT  8FT  6FT  4FT  2FT  [A] - Reinstall reflectors (if applicable) and internal gear tray. Install lamps (by others, if applicable).
 ROUGH OPENING   138.25”  115.00”  92.00”  69.25”  46.25”  23.25”  4  [B]  - Reinstall lens.
 LENGTH
 ROUGH OPENING
 WIDTH  (ACL) 2.50” - 2.63”, (D) 3.75” - 4.00”, (G) 5.25” - 5.50”