RECESSED TRIM FLANGE MOUNTING INSTALLATION GUIDE (XP)


 1  2


                                                        C

 OPTION 01
 A





 C
             A
 1


 B
                                                    B


                                A
 OPTION 02  3                                     4
 D/G JOINER

 A



 C
                                                                               A

 ACL1/4 JOINER




 B                                                                             B
              B

                                  C
                ACL2/3/5 JOINER
 INSTALLATION STEPS

 Attention: Risk of fire and electrical shock - fixture to be installed by qualified electrician according to local codes and ordinances.
 Attention: Ensure proper handling of LEDs to limit common problems including: broken connection, loose wiring, and damage from electrostatic discharge.
 1  [A] - Cut opening in ceiling. For nominal lengths, reference dimensions in chart below, or consult submittal drawings   2  ROWS
         for special lengths cut-outs.
               [A] - When rows are ordered, row sections will be labeled in sequence. Position section in proper
 [B] - Option 01 - Apply clamp above each top-hole section twisting into rough opening. Tighten 1/4-20 bolt (provided)           order prior to installation.
         to press together panels in between fixture flange and clamp flange. The bolts are to be tied to structure and if not   [B]  - Remove the lens. Apply suction cup (provided) to one end and carefully pull lens out.
         tie-off cables at each end cap must be attached to structure above.  [C] - Remove reflectors (if applicable) and internal gear tray by unfastening hardware.
         Option 02 - Use pre-drilled holes in top of fixture to attach 1/4-20 threaded rod (provided by others) and tie to
          structure. Draw fixture up snugly under bottom of ceiling slates/tiles and fasten with a flange nut.   [A] - Housing connection: White+, Black-, Green (if dimming is required): Purple Dim+, Grey Dim-
 [C]  - Power feed connections through KO hole: White+, Black-, Green (if dimming is required): Purple Dim+, Grey Dim-  3  [B]  - Align corner pins and connect fixture housings with rubber mallet until no gap remains.
               [C] - Secure sections with joiner screws.
 NOMINAL ROUGH OPENING DIMENSIONS:
 NOMINAL LENGTH  12FT  10FT  8FT  6FT  4FT  2FT  4  [A] - Reinstall reflectors (if applicable) and internal gear tray. Install lamps (by others, if applicable).
 ROUGH OPENING   138.25”  115.00”  92.00”  69.25”  46.25”  23.25”  [B]  - Reinstall lens.
 LENGTH
 ROUGH OPENING
 WIDTH  (ACL) 2.50” - 2.63”, (D) 3.75” - 4.00”, (G) 5.25” - 5.50”
 APPLICABLE LUMINAIRES: ACL5, ACL7, D5, D7, G5